Parameter Settings - Huawei UPS5000-S-35K User Manual

Singapore, 35 kva power modules
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)

4.2.2.3 Parameter Settings

Figure 4-53 Parameter settings
System Settings
Issue 02 (2020-01-10)
Item
Description
High ambient
An alarm is generated when the
temperature
ambient temperature reaches or
alarm threshold
exceeds the threshold specified
(° C)
by this parameter.
Low ambient
An alarm is generated when the
temperature
ambient temperature is lower
alarm threshold
than the threshold specified by
(° C)
this parameter.
EPO detection
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When EPO detection is changed
from Disable to Enable, check
that the EPO cable is connected
correctly.
Bus Capa. Life
If this parameter is set to Enable,
the UPS detects the bus capacitor
lifespan.
Paral. sys.
When customer loads are light,
hibernate
enable parallel hibernation to
alternate modules in hibernation
mode, which can prolong their
service life and improve the
system efficiency.
Module cycle
Indicates the rotation interval of
hiber. period
modules in hibernation mode.
(d)
The default value is 30, which
means that the hibernating
module is rotated every 30 days.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
55
40–60
–10
–20 to 0
Enable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
30
1–100
114