Single/Parallel and Output frequency must be correctly set. Otherwise, the UPS running
may be affected.
Output voltage level refers to the line voltage level.
Figure 5-1 Settings Wizard
Step 2 (Optional) On the MDU, choose System Info > Settings > DST Settings and set the DST
mode as required.
Step 3 After you set parameters on the Settings Wizard screen, the MDU displays the Bypass mode
and No battery alarms, which do not need to be handled. If there is any other alarm, you need
to rectify the fault.
Issue 05 (2019-12-24)
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
If dry contact signals are connected to the system, choose System Info > Settings > Dry contacts
Set and check that the connected dry contacts have been enabled and that the disconnected dry
contacts have been disabled.