UPS5000-A-400 kVA
User Manual (60 kVA, PF=0.9)
Item
Dis. cur. 0.3C
EOD (V/cell)
Dis. cur. 0.5C
EOD (V/cell)
Dis. cur. 1.0C
EOD (V/cell)
Sched. shallow
dis. test
Shallow dis.
test dis. ratio
(%)
iBOX Settings
Figure 4-27 iBOX settings
Issue 05 (2019-12-24)
Description
0.1C, 0.3C, 0.5C, and 1.0C
respectively.
When certain conditions are met,
the charger shuts down, and
batteries supply power to loads.
The system records the battery
discharge data as the reference
for battery capacity and lifespan.
Set the proportion of the
discharge capacity to the total
discharge capacity. The value is
configurable in any mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
1.80 V/cell
1.8–1.9
1.75 V/cell
1.75–1.85
1.60 V/cell
1.6–1.75
Disable
Disable, Enable
20%
10%–50%
106