UPS5000-A-400 kVA
User Manual (60 kVA, PF=0.9)
Item
Input system
Rated input
voltage
Input voltage
Rated
frequency
Input
frequency
Input PF
THDi
Table 8-6 Bypass Input Electrical Specifications
Item
Input system
Rated input
voltage
Rated
frequency
Input
frequency
range
Input system
Table 8-7 Battery Specifications
Item
Number of
batteries
Issue 05 (2019-12-24)
Specifications
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (line voltage)
80–280 V AC (phase voltage)
30° C < ambient temperature ≤ 40°C: The UPS supports full load when
the voltage is 198–280 V AC. The load bearing capacity is derated to
35% when the voltage is 198–80 V AC.
0°C ≤ ambient temperature ≤ 30°C: The UPS supports full load when
the voltage is 187–280 V AC. The load bearing capacity is derated to
35% when the voltage is 187–80 V AC.
50 Hz or 60 Hz
40–70 Hz
> 0.99 (full load)
> 0.98 (half load)
THDi < 3% (full linear load)
THDi < 5% (full non-linear load)
Specifications
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (line voltage)
50 Hz or 60 Hz
± 6 Hz (adjustable with the tolerance of 0.5–6 Hz, ± 2 Hz by default).
The mains input and bypass input can share a power source or use
different power sources.
Specifications
360V DC to 528V DC: 12 V batteries, 30–44 batteries (40 by default).If
there are 40–44 batteries, output power is not derated. If there are 38 or 36
batteries, output power is derated to 90%. If there are 34 or 32 batteries,
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
178