UPS5000-A-400 kVA
User Manual (60 kVA, PF=0.9)
Connect cables from top to bottom.
When connecting cables, tighten bolts from inside out to secure cables.
Before cable connections, ensure that all UPS input switches are OFF. Paste warning
labels to prevent operation on the switches.
Connect input power cables to the UPS and then to customer equipment.
Figure 3-20 Ground cable
Step 6 Connect the mains input power cables.