Huawei UPS5000-A-400 kVA User Manual page 49

Hide thumbs Also See for UPS5000-A-400 kVA:
Table of Contents

Advertisement

UPS5000-A-400 kVA
User Manual (60 kVA, PF=0.9)
When you connect power cables, comply with the tightening torque listed in the following
table to ensure secure connections and prevent safety risks.
Table 3-3 Power cable terminal requirements
Port
Connection
Description
Method
Mains input
Crimped DT
terminal
Bypass input
Crimped DT
terminal
Battery input
Crimped DT
terminal
Output
Crimped DT
terminal
PE
Crimped DT
terminal
Table 3-4 Recommended upstream input and downstream output circuit breakers
UPS Capacity
400K
a: Recommended specifications when the short-circuit current going through the circuit
breaker is less than 50 kA.
Issue 05 (2019-12-24)
In single mains scenario, the input cable should use the larger specifications between the
mains input and bypass input.
The recommended cables are used only when the following requirements are met:
90° C flexible copper power cable. Multi-core cables are recommended for mains
and bypass input and output power cables, and single-core cables are recommended
for battery cables.
Routing mode: Mains and bypass input and output power cables are routed over a
ladder or bracket (E in IEC60364-5-52), and battery cables are routed over a ladder
or bracket in a single layer (F in IEC60364-5-52).
The ambient temperature is 30° C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
Recommended cable lengths: AC power cable ≤ 30 m, DC power cable ≤ 50 m.
Bolt
Specifications
M16
M16
M16
M16
M12
Copyright © Huawei Technologies Co., Ltd.
Bolt Hole
Diameter
18 mm
18 mm
18 mm
18 mm
/
Circuit Breaker Name
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Bolt Length
Torque
50 mm
120 N· m
50 mm
120 N· m
50 mm
120 N· m
50 mm
120 N· m
35 mm
47 N· m
Specifications
800 A/3P
800 A/3P
800 A/3P
3 Installation
a
41

Advertisement

Table of Contents
loading