Huawei UPS5000-A-400 kVA User Manual page 203

Hide thumbs Also See for UPS5000-A-400 kVA:
Table of Contents

Advertisement

UPS5000-A-400 kVA
User Manual (60 kVA, PF=0.9)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0150-1
Inverter
asynchronous
0101-1
BSC signal
abnormal
0102-1
Maint. breaker
misoperation
0380
In self-check
Issue 05 (2019-12-24)
Severity
Cause
The bypass SCR
open-circuits.
Minor
The bypass
frequency
changes fast.
The output
frequency track
rate is incorrectly
set.
Minor
The dual bus
connector is
loose.
Parameters are
set incorrectly.
Critical
The user operation is
incorrect.
Warning
The inverter is in
self-check.
Copyright © Huawei Technologies Co., Ltd.
B Alarm List
Solution
1. Check that the bypass output
frequency does not change
fast.
2. Check that the Output freq.
track rate is properly set.
1. Check the dual bus connector.
2. Check the parameter settings.
3. The master BSC system is not
supplying power.
1. Shut down the inverter and
then close the maintenance
circuit breaker.
2. After maintenance, open the
maintenance circuit breaker
and then start the inverter.
Wait until the inverter self-check
is complete.
195