Item
Table 8-9 System Electrical Specifications
Item
Redundancy
design
ECO
Issue 05 (2019-12-24)
Specifications
125% < linear load ≤ 150%: transfer to bypass mode after 30 seconds.
Linear load > 150%, and short circuit: run for 200 ms.
Specifications
Control units and parallel signals use a redundancy design.
Supported