Table 4-12 Monitoring details

4.2.2.1 Parameter Settings

Figure 4-47 Parameter settings
System Settings
Issue 02 (2020-01-10)
Number
Area
1
Running status
area
2
Menu bar
3
Information
area
Item
Description
High ambient
An alarm is generated when the
temperature
ambient temperature reaches or
alarm threshold
exceeds the threshold specified
(° C)
by this parameter.
Low ambient
An alarm is generated when the
temperature
ambient temperature is lower
alarm threshold
than the threshold specified by
(° C)
this parameter.
EPO detection
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When EPO detection is changed
from Disable to Enable, check
that the EPO cable is connected
correctly.
Bus capa. life
If this parameter is set to Enable,
Copyright © Huawei Technologies Co., Ltd.
Function
Displays the power flow and UPS running information.
Displays alarms and real-time data, sets parameters, and
provides control commands.
The Active Alarms page is displayed by default.
Displays system monitoring information.
4 User Interface
Default Value
Value Range
55
40–60
–10
–20 to 0
Enable
Disable, Enable
Disable
Disable, Enable
128