4.3.2.1 Parameter Settings

Figure 4-48 Parameter settings
System Settings
Item
High ambient
temperature
alarm threshold
(° C)
Low ambient
temperature
alarm threshold
(° C)
EPO detection
Bus capa. life
Issue 03 (2020-04-27)
Area
Function
Running status
Displays the power flow and UPS running information.
area
Menu bar
Displays alarms and real-time data, sets parameters, and
provides control commands.
The Active Alarms page is displayed by default.
Information
Displays system monitoring information.
area
Description
An alarm is generated when the
ambient temperature reaches or
exceeds the threshold specified
by this parameter.
An alarm is generated when the
ambient temperature is lower
than the threshold specified by
this parameter.
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When EPO detection is changed
from Disable to Enable, check
that the EPO cable is connected
correctly.
If this parameter is set to Enable,
the UPS detects the bus capacitor
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
55
40–60
–10
–20 to 0
Disable
Disable, Enable
Disable
Disable, Enable
139