12. Repeat Steps 1 through 11 for all circuits.
Choices
Enter Point
Select Type
Select Type
Select Zone/Group
Edit Name
* Only applicable for 5895XL
9.5.4 Point Programming For 5880 or 5865 Modules
To program 5880 or 5865 module points:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
121
Function Selections
Type Selections
for each Type
UNUSED
B NOTIF
NOTIF OUTPUT
CONTROL CIRCUIT
A NOTIF
Same as B NOTIF
AUX_PWR
CONSTANT
AUX RESET
AUX DOOR
AUX SYNC
B SWITCH*
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
ECS INPUT
ECS TAMPER
ECS SUPERVISORY
A SWITCH*
Same as B SWITCH
B DETECT*
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
A DETECT*
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
Table 9.6 Menu choices for Internal/External Power Module
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Comments
User also has Supervised/
Unsupervised option
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Power Sync
Refer to comments column of
Table 9.4 for description of these options.
Latch or Non-latching feature only appears
for WATERFLOW, FIRE SUPERVISORY,
FIRE TAMPER, ZONE AUX1, ZONE AUX2,
SYSTEM AUX1, SYSTEM AUX2, ECS
INPUT, ECS TAMPER, and ECS
SUPERVISORY.
User also has ECS Event Number 1-8 option
for ECS INPUT.
Only available when an ECS-VCM or ECS-
NVCM is installed in the system.
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-
wire CO Supervisory detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Group or Zone selection will appear
depending on the type selected.
See "Editing Text Using the Built-In
Programmer" on page 195.