7.
Select one of the following options from the menu that displays.
1- Review System
2- Repeat JumpStart
3- Accept Configuration
4 - Discard Changes

8.2 Mapping Overview

This section of the manual is an overview of mapping.
Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events to outputs that will acti-
vate when events occur. You do this by assigning input points to input zones, output points to output groups and then linking or mapping
zones and output groups.
Figure 8.1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Press 1 if you need to review the JumpStart configuration. The Review System menu will appear. Press 1
to review Entire System or Press 2 for Changes Only.
Press 2 if you need to rerun JumpStart for any reason.
1.
If you are ready to make the JumpStart configuration permanent, select 3.
2.
The system will ask you if the installation contains any Addressable Duct Detectors Used. If there
are none, select 2 for No and skip to Step 8. If the system contains duct detectors, select 1 for Yes
and continue with Step 3.
3.
From the list that displays, select the SLC that contains the duct detectors.
4.
The first photoelectric or ionization detector on the system will display. Select 1 for DUCT and 2 for
NonDUCT.
5.
Press up arrow to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue until all
duct detectors have been selected. (Note: You can move backwards through the list with down
arrow).
6.
When you reach the last detector on this device, press left arrow.
7.
The system will ask you if there are any duct detectors used. If there are, select 1 for Yes and the
message will ask, Have All Addressable Duct Detectors Been Identified? Left arrow for "No", Right
arrow for "Yes". If there are no more duct detectors, continue with Step 8.
8.
The system will restart with the saved JumpStart configuration.
9.
After the system resets, it will use the new JumpStart configuration.
If you want to discard the changes, and keep the configuration you had before running this JumpStart
press 4.
Figure 8.1 Mapping Overview
88