Zone; 1: Edit Zone; Edit Zone Name; Edit Zone Properties - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

9.3 Zone

Through the zone option in the program menu you can edit and view zone points. Selections made here affect all detectors and switches
in the zone. Up to 250 zones can be used in the system.
9.3.1 Edit Zone
Features that can be edited through the edit zone option are zone name, zone properties (which includes, zone type, and detector sensitiv-
ity), zone output mapping, and zone accessory options.
To edit a zone, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 2 to enter zone menu.
4.
Press 1 to edit a zone.
5.
Enter the zone number, then press ENTER.

Edit Zone Name

6.
Press 1 to edit the selected zone name.
You can use words to display a descriptive name for a zone.
NOTE: See Appendix B for editing names

Edit Zone Properties

Zone properties consist of alarm delay characteristics, and heat detector sensitivity, and smoke detector sensitivity.
1.
Do steps 1 through 5 of Section 9.3.1.
2.
Press 2 to edit the properties of the selected zone.
NOTE: You only see smoke sensitivity on the IFP-300/ECS if the daytime/nighttime sensitivity is off under System Options. (See Section
9.6.2). Otherwise if you have Daytime/Nighttime sensitivity on, this will bring up a Smoke Sens Day and Night, 2 separate widgets with sensitivity
as being either low, med high for each
Alarm Delay Characteristics
The programmed zone type is provided for user reference only. To modify the zone type use the HFSS Honeywell Fire Software Suite.
Select the alarm delay characteristics (see Table 9.1) by pressing the up or down arrow.
Type of Delay
1-Count
2-Count
111
Figure 9.2 Editing Zone Properties
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device of
any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is
considered the most typical operation and is the default for all zones.
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order for
the zone to report an alarm. Switches of type manual pull, water flow, Detector Switch, Aux1 and Aux2 are
an exception; they will cause an alarm when only one switch is in alarm.
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a prealarm
condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has occurred. If
the zone has been mapped to an output group for the prealarm event, the output group will activate. The
prealarm will not be reported to the central station.
Table 9.1 Alarm Delay Types
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Description

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-300Farenhyt ifp-300ecs

Table of Contents