3: Current Draw Worksheet For Sk Slc Devices - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Notification Appliance Circuits
5495/5499 Power Supply
C Notification Appliances Current
D Total current ratings of all devices in system (line A + line B + C)
E Total current ratings converted to amperes (line D x .001):
F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
G Multiply lines E and F.
H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
I
Multiply lines E and H.
J Add lines G and I.
Multiply by the Derating Factor
1. The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
2. IDP-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. This should be considered when
determining auxiliary power capacity but not calculated into current requirements for day to day operation.
3. The IDP-PhotoR is sold separately from the DNR. Current draw for the DNR + IDP-PhotoR is calculated by increasing the "Number
of Devices" column for each IDP-PhotoR used with a DNR.
4. The DNR housing does not include a Relay circuit board. If a relay is needed, be sure to add one to the IDP-Relay & IDP-PhotoR
"Number of Devices" column for each DNR used for correct current calculations.
5. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be
drawn from the panel.
6. Use next size battery with capacity greater than required.
7. Total does not include isolator devices or accessory bases.
3.7.3 Current Draw Worksheet for SK SLC Devices
Use Table 3.3 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. The IFP-
300 FACP supports up to a total of 300 SLC devices, consisting of any combination of Sensors and Modules.
For each device use this formula:
Fire Panel (Current draw from battery) 1
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Number of
Device
Devices
Refer to devices manual for current rating.
6
Table 3.2 Current Draw Worksheet for IDP SLC Devices
Number of
Device
Devices
This column
Table 3.3 Current Draw Worksheet for SK SLC Devices
Current per Device
24 VDC
One input circuit:
Both input circuit
Alarm:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Total ampere hours required
Current per Device
X
This column
=
Standby:
Alarm:
Standby
Current
15 mA
30 mA
mA
mA
mA
mA
mA
A
H
AH
AH
x 1.25
6
Standby
Current
Current per number of devices.
190 mA
190 mA
250 mA
Alarm
Current
mA
mA
mA
mA
mA
mA
mA
mA
A
H
AH
Alarm
Current
250 mA