8.2.5 Mapping LED Points for a Networked System
8.3 Programming Using the HFSS Software Suite
You can use the HFSS Honeywell Fire Software Suite to program the control panel onsite (personnel will need to be onsite during the
upload or download process). HFSS is a software package that lets you easily program the control panel using a Windows-based com-
puter. HFSS is needed for Mapping. When using HFSS, you can set up the programming options for the panel, save the options in a file,
then download the file to the panel. You can connect to the control panel directly using the onboard USB. Updates are available at
www.farenhyt.com
8.4 Programming Using an Annunciator
You can program the control panel from a system annunciator, using either the control panel's on-board annunciator or an RA-100, RA-
1000 or RA-2000 remote annunciator.
The following subsections describe programming basics, including a description of editing keys available for programming and how to
move through programming menus. Section 9 contains specific information about individual programming options.
8.4.1 Entering / Exiting the Panel Programming
To enter Programming Mode:
1.
Enter the Installer Code (factory programmed default code is 123456).
2.
Select 7 for Programming Menu. See Section 9 for detailed information and Section 8.5 for a quick reference listing all
programmable options and JumpStart defaults.
To exit the programming menu:
When you have completed working with the menus, press left arrow several times until you are exited from programming mode. Two
prompts will display. The first prompt is to make sure you intended to leave the Program Menu (select Yes or No as appropriate). The
second prompt is for accepting all changes. If you select No, any changes you have made since you entered the Program Menu will have
no effect.
95
Figure 8.8 Example of Expanding Mapping of LED Points Across Panels
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017