Honeywell Farenhyt Series Installation And Operation Manual page 121

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Type Selection
SWITCH
(cont.)
NOTIF
RELAY
SLC LED
9.5.2 Point Programming For 6815 Module
To program for points on an 6815 module, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
117
Function
Latching Option
ZONE AUX1
Latching
Non Latching
ZONE AUX2
Latching
Non Latching
SYSTEM AUX1
Latching
Non Latching
SYSTEM AUX2
Latching
Non Latching
DETECTOR
FIRE TAMPER
Latching
Non Latching
MANUAL
RELEASE
INTERLOCK
STATUS POINT
ECS INPUT
Latching
Non Latching
ECS TAMPER
Latching
Non Latching
ECS SUPER-
Latching
VISORY
Non Latching
CO DETECT
SWITCH
CO
Latching
SUPERVISORY
Non Latching
DETECT SWITCH
OUTPUT PT
Select Group
AUX CONST
AUX RESET
AUX DOOR
OUTPUT PT
Select Group
AUX RESET
AUX DOOR
LED NUMBER
01-80
LED FUNCTION
Unused
NOTIF
Table 9.4 Programming Options for 5815XL Modules
Use these switch types if you want to monitor special zone-level
conditions (such as dry contact from a remote power supply).
Use these switch types if you want to monitor special system-wide
conditions (such as dry contact from a remote power supply).
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
Performs identically to a supervisory switch, but will be indicated as
a tamper switch on the LCD annunciator.
Manual release switch
Interlock release switch input.
User also has ECS Event Number 1-8 option for ECS INPUT.
Only available when an ECS-VCM is installed in the system.
CO Detector Switch
CO Supervisory Detector Switch
Output point, a general use notification type. Use for driving
standard notification appliances.
Use constant power for applications that require a constant auxiliary
power source. Power is always present at constant circuits.
Use for auxiliary power, resettable applications. See Section
"Auxiliary Power Installation" on page 52 for a description of how
this option operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section "Door Holder Power" on page 52
for a description of how this option operates.
Output point, a general use relay type. Use for applications requiring
a relay, such as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section
"Resettable Power" on page 52 for a description of how this option
operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section "Door Holder Power" on page 52
for a description of how this option operates.
For use with SD devices only. 80 sub addresses on LED.
Notification can have group number.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017