9: Silence Alarms Or Troubles; 10: Reset Alarms; Reset Communicator; 11: Check Detector Sensitivity Through Point Status - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

10.4.9 Silence Alarms or Troubles
Press SILENCE to turn off silenceable outputs and annunciator PZTs. If an external silence switch has been installed, activating the
switch will silence fire alarms or troubles. If you are already using system menus when you press SILENCE, you will not need to enter
your code.
NOTE: Alarm and trouble signals that have been silenced, but the detector remains un-restored, will un-silence every 4 or 24 hours depending
on user selection (see section "Auto-Resound (4 or 24 hours)" on page 129) until the detector is restored.
NOTE: Multi-Site displays do not allow for silencing multiple sites. Pressing SILENCE will only locally silence the PZT built into the
annunciator. To silence a site, enter a multi-site access password, select a site, and then press SILENCE.
NOTE: For ECS systems, pressing silence at an LOC will only silence the System in Control. See Section 10.5.1.
10.4.10 Reset Alarms
Press RESET to perform a control panel reset. If an external reset switch has been installed, activating the switch will reset fire alarms.
NOTE: Multi-Site displays do not allow for resetting multiple sites. To reset a site, enter a multi-site access password, select a site, and then
press RESET.
NOTE: For ECS systems, pressing reset at an LOC will prompt the user for which system they desire to reset. See Section 10.5.1

Reset Communicator

This options allows the user to Reset the communicator. The LCD will display:
"Resetting Communicator... Please Wait"
You will be returned to the Main Menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the
following are active:
Fire Alarm
Fire Supervisory
Fire Pre-Alarm
CO Alarm
CO Supervisory
ECS Alarm
ECS Supervisory
10.4.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a
CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the central station receives a detector trouble report ("373" and the zone or point for Contact ID
format; "FT" and the zone or point in SIA format).
To check sensitivity for an individual detector, follow the steps below.
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press ENTER.
137
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-300Farenhyt ifp-300ecs

Table of Contents