Pressing Select Key 5 will start a playback of the recorded message.
Press
Select Key 5
to record to
this message
slot
11.8.3 Erasing User Message
To erase the message stored in switch 1-15 memory location follow these steps:
1.
Enter programming mode at main control panel.
2.
Select option 8 Voice Options.
3.
Select option 1 VCM Maintenance.
4.
Select option 2 Local Recording. Once in this mode, the VCM/RVM will light all the green LEDs for switches 1-15 indicating
which message slots are occupied.
5.
Select the amplifier and circuit for the audio to play through during programming. A user would generally pick the audio circuit that
is in closest proximity to them
6.
Press ECS Message Key 8 on the VCM, press the Select Key 1-15 that you wish to erase. The Select Key red LED will stay on until
the erase is done. When erased, the Select Key green LED by corresponding to the message slot you erased will go off.
11.8.4 Using HFSS Voice Message Load Software
The HFSS Voice Message Load Software is a software support utility that is used to download recorded messages (in .SKE format stored
on your PC hard drive) to the various message locations of the ECS-Series VCM or ECS-NVCM. Messages can be uploaded from the
ECS-VCM or ECS-NVCM, stored, and used again in similar installations.
To read/write .SKE formatted messages to and from the main panel, follow these steps:
1.
Make sure that panel is in Normal mode.
159
Figure 11.7 Recording with Microphone Example
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Press
ECS Message
Key to enter
message slot
selection mode