4: Computer Access; 5: Access Codes - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

To Edit the Network Panel ID:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 6 for Network Programming.
3.
Press 3 to enter the Edit Panel ID menu.
4.
If the Network Panel ID is changed and valid, the system will ask you to confirm the change. If it is not correct, you can change the
dip switches at this time.
5.
Press up to select YES and press ENTER to confirm.
6.2.4 Computer Access
An installer at the panel site can initiate communications between the panel and a computer running the HFSS Honeywell Fire Software
Suite (see also Section 10.5). In order for this communication to function properly, both the computer (running the software) and the con-
trol panel must have matching computer access numbers and computer codes.
To program computer access information:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 6 for Network Programming.
3.
Press 4 to enter the Computer Access menu.
4.
Enter the computer access number (up to 6-digits), then press ENTER.
5.
Enter the computer code, then press ENTER.
6.
Enter the computer phone number, the panel will dial to connect to a downloading computer (up to 40-digits), then press ENTER.
6.2.5 Access Codes
Access codes provide the user access to the control panel functions. Each access code can be customized for each user. This allows some
users the ability to access programming and other higher level panel functions, while other users may only need access to lower level
functions such as preforming fire drills, or acknowledging trouble conditions.
Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to. Because this is the profile for a key, the user name
and the access code can not be edited for this profile.
Profile 2 is the profile for the installer and is referred to as the "Installer Code". This profile's user name and panel functions can not be
edited. Table 6.1 lists the panel functions that can be selected for each user profile.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Type of Function
Panel Operations
User Profile Selectable Panel Functions
Table 6.1
Selectable Functions
System Reset
System Silence
System Ack
Fire Drill Key
Multi-site
F1 Function Key
F2 Function Key
F3 Function Key
F4 Function Key
ECS Control Request Function
ECS Super User Function
68

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-300Farenhyt ifp-300ecs

Table of Contents