7.8 Addressing IDP or SK SLC Devices
All IDP or SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones
place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two or three digit number.
The control panel recognizes when an IDP /SK detector or IDP/SK module is installed. For this reason, IDP/SK detectors can be
assigned any unique address from 1 to 159, and IDP/SK modules can be assigned any unique address from 1 to 159. There can be an
IDP/SK detector using address 1 and an IDP/SK module using address 1. 0 is an invalid address. In order to set the sensor above address
99, carefully remove the stop on the upper rotary switch with thumb as shown in Example 2.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in "IDP or SK SLC
Device Addressing Using Rotary Dials" on page 82.
Example 2: To select device address 105, turn the ONES rotary dial to 5 and the TENS rotary dial to 10 as show in "IDP or SK SLC
Device Addressing Using Rotary Dials" on page 82.
7.9 Wiring SD Detectors
The information in this section applies to the following SD models, see Table 7.3 for list of devices.
To Wire SD Detectors
1.
Wire device bases as shown in Figure 7.5.
2.
Set the address for each device as described in Section 7.10.
7.10 Addressing SD Devices
This section tells how to address detectors and modules. See Table 7.3 for a list of detectors that are easily addressed at the FACP. The
Installer Code is required to perform this task.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
All dials labeled for ONES
or TENS position.
Figure 7.4 IDP or SK SLC Device Addressing Using Rotary Dials
Figure 7.5 Heat or Smoke Detector Connection to the FACP
Example 2: Device Set to 105.
82