2: View Group Points; 3: Edit Opg Template - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Dynamic Activation / Template Override Cadence. (This is shown when the Template override is set to Yes or if a non-voice group
is assigned a Select/Dynamic Activation switch number): this setting sets the cadence of the non-voice group mapped to voice
select switch when activated using dynamic activation or by a template.
Defining Output Group Type
Each output group is defined as either a voice output group or a non-voice output group. Output points that are
audio circuits (all circuits on the ECS-50W, ECS-125W, ECS-DUAL-50W, ECS-INT50W and ECS-CE4) can only be assigned to voice
output groups. Output points that are non-voice circuits (all other points and circuits that are on all modules except the ECS-50W, ECS-
125W, ECS-DUAL-50W, ECS-INT50W and ECS-CE4) are assigned to non-voice output groups.
Each of the output groups defined as voice can be mapped to a particular switch and LED on the ECS-VCM/ECS-NVCM, ECS-RVM
and ECS-SW24. This allows the user to see the state of the voice groups assigned to the switches.
This also lets the user individually select which areas they want to do a live page into. Output groups not defined as voice groups can
also be assigned to these switches as long as there is a voice group already assigned to the group. This allows for dynamically activat-
ing/deactivating both voice and strobes/other outputs in an area with a single button press. See "Activating/Deactivating Output Groups
Dynamically" on page 151..
Silencing Options
The following silencing options are available for each output group.
Optional Timers
Silence Inhibit
Auto Silence
Auto Unsilence
Startup Delay
9.4.2 View Group Points
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 2 to view group points.
5.
Enter the group number, then press ENTER.
9.4.3 Edit OPG Template
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 3 to edit OPG Template.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Corresponding
Key and LED Numbers
ECS User Interface
Figure 9.3 Corresponding Key and LED for Mapping Output Groups
Timed Silence after Inhibit. If this option is selected, the output group must be audible for a programmed
number of minutes before it can be silenced. If the condition that caused the output to activate has not
cleared during the time-frame, the output can be silenced. If you select this option, select the timeframe in
the delay field. Range is 0-60 minutes.
Silenceable. The output group will automatically silence after the timer expires. Range is 0-60 minutes.
If this option is selected, the output group can be silenced for a programmed time-frame. If the condition that
caused the output to activate has not cleared during the time-frame, the output reactivates. If you select this
option, select the time-frame in the delay field. Range is 0-60 minutes.
When a alarm is generated, the Output group will not activate until the timer expires assuming the event is
still active. Range is 0-120 Seconds
Table 9.3 Silencing Options
Corresponding
Key and LED Numbers
ECS-SW24
Description
114