Honeywell Farenhyt Series Installation And Operation Manual page 89

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

To address:
1.
Connect a detector base temporarily to the programming terminals as shown in Figure 7.6. (You can use the same base for each
detector.)
2.
Enter the Installer code, then press ENTER.
3.
Select 2 for Point Functions.
4.
Select 3 for Set SLC Dev Address.
5.
Select "Yes" by pressing the up arrow, then press ENTER. (The panel will go into trouble at this point. You can use the SILENCE
key to stop the PZT. The trouble will clear automatically when the panel reinitializes when you finish programming.)
6.
When the wait message clears, the following options display:
1- for Read Address. Use to read (or check) a single detector's address.
2- for Write Address. Use to program a single detector's address.
3- for Seq. Programming. Use to program more than one detector in sequential order.
7.
If you are changing addresses, write the programmed address on the back of the device.
8.
To exit press left arrow until fully exited.
83
Figure 7.6 Temporary Connection of Detector Base to Panel for Addressing
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017