Honeywell Farenhyt Series Installation And Operation Manual page 124

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Type Selection
SWITCH
(cont.)
NOTIF
RELAY
Detector
W-Gateway
W-SWITCH
W-Relay
9.5.3 Point Programming For Internal or External Power Module (RPS-1000)
To program for an internal or external power module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section "Programming Menu Quick Reference" on page 97
for available choices, then press ENTER.
5.
Enter the number of the circuit or point you wish to edit, then press ENTER.
6.
Select the type by pressing the up or down arrow key, then press ENTER.
7.
Select the function by pressing the up or down arrow key, then press ENTER.
8.
If the point supports latching press the up or down arrow key to select latching or non-latching, then press ENTER.
9.
Select the zone or group by pressing the up or down arrow key, then press ENTER.
10. If the point supports not being supervised, press the up or down arrow key to select supervised or non-supervised, then press
ENTER.
11. Press ENTER to edit point name. See "Editing Text Using the Built-In Programmer" on page 195. Or, Press right arrow key to skip
point name edit.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Function
Latching Option
ECS INPUT
Latching
Non Latching
ECS TAMPER
Latching
Non Latching
ECS SUPER-
Latching
VISORY
Non Latching
CO DETECT
SWITCH
CO
Latching
SUPERVISORY
Non Latching
DETECT SWITCH
OUTPUT PT
Select Group
AUX CONST
AUX RESET
AUX DOOR
OUTPUT PT
Select Group
AUX RESET
AUX DOOR
2-Wire Smoke
Same as SWITCH
Same as Relay
Table 9.5 Programming Options for 6815 Modules
Comments
User also has ECS Event Number 1-8 option for ECS INPUT.
Only available when an ECS-VCM or ECS-NVCM is installed in the
system.
CO Detector Switch
CO Supervisory Detector Switch
Output point, a general use notification type. Use for driving
standard notification appliances.
Use constant power for applications that require a constant auxiliary
power source. Power is always present at constant circuits.
Use for auxiliary power, resettable applications. See Section
"Auxiliary Power Installation" on page 52 for a description of how
this option operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section "Door Holder Power" on page 52
for a description of how this option operates.
Output point, a general use relay type. Use for applications requiring
a relay, such as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section
"Resettable Power" on page 52 for a description of how this option
operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section "Door Holder Power" on page 52
for a description of how this option operates.
Wireless Gateway
When a wireless relay is in use, module device count must be
limited to 109 modules per loop. This includes wired and wireless
modules that are on the same loop. The module address must be
within 1-109.