Danfoss DSH090 Application Manual

Danfoss DSH090 Application Manual

Scroll compressors
Hide thumbs Also See for DSH090:
Table of Contents

Advertisement

Quick Links

Application Guide
Scroll compressors
DSH090 to DSH600
R410A - R454B - R452B, 50Hz -60Hz
www.danfoss.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DSH090 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss DSH090

  • Page 1 Application Guide Scroll compressors DSH090 to DSH600 R410A - R454B - R452B, 50Hz -60Hz www.danfoss.com...
  • Page 2: Table Of Contents

    Scroll compressors, DSH090 to DSH600 | Contents Contents Safety and warnings Introduction Product description Cut Away DSH090-184 Cut Away DSH240-600 How do IDVs work? Product identification Name Plate Nomenclature Compressors serial number Certificates, declarations and approvals Certificates, declarations, and approvals...
  • Page 3 Scroll compressors, DSH090 to DSH600 | Contents Operating envelope Dimensions Single compressors Tandem assemblies Trio assemblies Mechanical connections Connection Details Design compressor mounting Design piping Electrical connections Wiring connections Electrical Specifications Application Manage oil in the circuit Manage sound and vibration...
  • Page 4 Scroll compressors, DSH090 to DSH600 | Contents Solder sleeve Rotolock nut Motor protection modules Crankcase heaters Discharge temperature protection Mounting hardware Lubricant Terminal boxes, covers and T-block connectors Acoustic hoods Miscellaneous Tandem kits Trio kits Updates Online support © Danfoss | Climate Solutions | 2022.10...
  • Page 5: Safety And Warnings

    The purpose of this guideline is to help customers qualify compressors in the unit. You are strongly advise to follow these instructions. For any deviation from the guidelines, please contact Danfoss Technical Support. In any case, Danfoss accepts no liability as a result of the improper integration of the compressor into the unit by the system manufacturer.
  • Page 6: Introduction

    Introduction Product description Danfoss scroll compressor DSH for R410A, R454B and R452B is available as single compressor and can be assembled in tandem or trio combinations. DSH series scroll compressor benefit from an improved design to achieve the highest efficiency and increased life time.
  • Page 7: Cut Away Dsh240-600

    How do IDVs work? Figure 3: Intermediate Discharge Valve (IDV) Danfoss Intermediate Discharge Valves (IDVs) are located close to the discharge side of the compressor. They reduce excessive compression of refrigerant under part-load conditions while maintaining the same cooling capacity. The IDVs open when discharge pressure falls below the built-in optimization point.
  • Page 8: Product Identification

    Scroll compressors, DSH090 to DSH600 | Product identification Product identification Name Plate Figure 4: Name Plate Model number Serial number DSH485B4APC Model no : M A D E I N F R A N C E Approvals 380-415V 3~50Hz JC112345678...
  • Page 9: Compressors Serial Number

    Scroll compressors, DSH090 to DSH600 | Product identification Compressors serial number 12345678 Year code 8 Digit serial number Month code Plant assembly line code Table 1: Serial number code legend table Year code Month code Plant assembly line code Year...
  • Page 10: Certificates, Declarations And Approvals

    Scroll compressors, DSH090 to DSH600 | Certificates, declarations and approvals Certificates, declarations and approvals Certificates, declarations, and approvals DSH scroll compressors comply with the following approvals and certificates. Certificate are listed on: Documentation for Commercial Compressor | Danfoss Table 2: Certificates, declarations, and approvals...
  • Page 11: Refrigerants

    Scroll compressors, DSH090 to DSH600 | Refrigerants Refrigerants General Information When choosing a refrigerant, different aspects must be taken into consideration: • Legislation (now and in the future) • Safety • Application envelope in relation to expected running conditions • Compressor capacity and efficiency •...
  • Page 12: Technical Specification

    Scroll compressors, DSH090 to DSH600 | Technical specification Technical specification 50-60 Hz data Single compressor Table 7: Technical specification 50-60 Hz data Single compressor Nominal Swept volume Displacement (50 Hz) Displacement (60 Hz) Oil charge Net weight tons 60 Hz...
  • Page 13: Performance Data

    Scroll compressors, DSH090 to DSH600 | Performance data Performance data R410A 50-60 Hz, Single compressor Table 8: 50-60 Hz Performance data Nominal tons Nominal cooling capacity Power input E.E.R. 60 Hz Model Btu/h Btu/h/W DSH090 20048 68402 6.57 3.05 10.40...
  • Page 14: R452B 50-60 Hz, Single Compressor

    Scroll compressors, DSH090 to DSH600 | Performance data R452B 50-60 Hz, Single compressor Table 9: 50-60 Hz Performance data Nominal cooling capacity Power input E.E.R. Model Btu/h Btu/h/W DSH090 19590 66839 6.46 3.03 10.35 DSH105 23451 80016 7.40 3.17 10.81...
  • Page 15: R454B 50-60 Hz, Single Compressor

    Scroll compressors, DSH090 to DSH600 | Performance data R454B 50-60 Hz, Single compressor Table 10: 50-60 Hz Performance data Nominal cooling capacity Power input E.E.R. Model Btu/h Btu/h/W DSH090 19346 66010 6.37 3.03 10.36 DSH105 22940 78270 7.26 3.16 10.78...
  • Page 16: Sound And Vibration Data

    Scroll compressors, DSH090 to DSH600 | Sound and vibration data Sound and vibration data Typical sounds and vibrations in systems can be broken down into the following three categories: • Sound radiation (through air) • Mechanical vibrations (through parts and structure) •...
  • Page 17: Mechanical Vibrations

    A compressor generates some vibrations that propagate into the surrounding parts and structure. The vibration level of a DSH compressor alone does not exceed 120µm peak to peak for DSH090 to DSH184, and 154µm peak to peak for DSH240 to DSH600. However, when system structure natural frequencies are close to running frequency, vibrations are amplified due to resonance phenomenon.
  • Page 18: Operating Envelope Data

    Scroll compressors, DSH090 to DSH600 | Operating envelope data Operating envelope data Operating envelope for DSH scroll compressors guarantees reliable operations of the compressor for steady- state operation. Steady-state operation envelope is valid for a suction superheat within 5K to 30K range at nominal Voltage.
  • Page 19 Scroll compressors, DSH090 to DSH600 | Operating envelope data Figure 7: R452B / R454B - DSH090 to DSH105 (Max. DGT 150°C) Evaporating temperature (°F) S.H. = 5 K (9°F) S.H. = 30 K (54°F) Evaporating temperature (°C) CC-000039 Figure 8: R452B / R454B - DSH120 to DSH184 (Max. DGT 150°C) Evaporating temperature (°F)
  • Page 20 Scroll compressors, DSH090 to DSH600 | Operating envelope data Figure 9: R452B / R454B - DSH240 to DSH600 ( Max. DGT 150°C) Evaporating temperature (°F) S.H. = 5 K (9°F) S.H. = 30 K (54°F) Evaporating temperature (°C) CC-000041  NOTE: The application envelope of a cross-platform manifold results in the conjunction of map limitations of compressors composing the tandem.
  • Page 21: Dimensions

    Scroll compressors, DSH090 to DSH600 | Dimensions Dimensions Single compressors Figure 10: Outline drawing number 1 Figure 11: Outline drawing number 2 Figure 12: Outline drawing number 3 Ø D Ø D Ø D 190.5mm Ø19.05mm (7.5 inch) (0.75 inch) 30°...
  • Page 22: Tandem Assemblies

    Scroll compressors, DSH090 to DSH600 | Dimensions Tandem assemblies Figure 13: Outline drawing number 1 Figure 14: Outline drawing number 2 Figure 15: Outline drawing number 3 Figure 16: Outline drawing number 4 Figure 17: Outline drawing number 5 Table 15: Tandem assemblies Motor Tandem mod‐...
  • Page 23 Scroll compressors, DSH090 to DSH600 | Dimensions Motor Tandem mod‐ Outline drawing voltage Composition number inch inch inch inch inch code 15.2 / DSH368E 4/3, 7, 9 DSH184 + DSH184 33.46 386 / 428 22.83 9.45 9.53 8560113 16.85 DSH360X...
  • Page 24: Trio Assemblies

    Scroll compressors, DSH090 to DSH600 | Dimensions Trio assemblies Figure 18: Outline drawing number 6 Figure 19: Outline drawing number 7 Figure 20: Outline drawing number 8 Figure 21: Outline drawing number 9 Table 16: Trio assemblies L1 (Minimum) Motor votlage...
  • Page 25 Scroll compressors, DSH090 to DSH600 | Dimensions  NOTE: Trio to be achieved by assembly of individual compressors © Danfoss | Climate Solutions | 2022.10 AB288965961751en-001402 | 25...
  • Page 26: Mechanical Connections

    Scroll compressors, DSH090 to DSH600 | Mechanical connections Mechanical connections Connection Details Table 17: Connection Details Connection Details DSH090 DSH105-120-140-161-184 DSH240-295-381 DSH485 DSH600 Suction connection Brazed 1"1/8 Brazed 1"3/8 Brazed 1"5/8 Brazed 1"5/8 Brazed 2"1/8 Discharge connection Brazed 7/8" Brazed 7/8"...
  • Page 27 The grommets must be compressed until contact between the flat washer and the steel mounting sleeve is established. The required bolt size for the DSH090-105-120-140-161-184 compressors is HM8-40. This bolt must be tightened to a torque of 15Nm.
  • Page 28 Scroll compressors, DSH090 to DSH600 | Mechanical connections Manifolding requirements DSH180E-210E-240E-280E-322E-368E and DSH260U-281U-301U mounting The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be installed below the rails. The rigid mounting spacers are included in tandem accessory kits. The rubber grommets are supplied with compressor.
  • Page 29 Scroll compressors, DSH090 to DSH600 | Mechanical connections Tightening torque 15Nm Additional rigid spacer (Refer to table below) Not supplied HM8mm 0.31 inch Supplied with the compressor Tightening torque 15 Nm Included in manifolding kit 4mm (0.16 inch) Thickness Not supplied...
  • Page 30 Scroll compressors, DSH090 to DSH600 | Mechanical connections Figure 29: DSH240-295-381 mounting Figure 30: DSH120-161-184 mounting Tightening torque 16Nm Tightening torque 15Nm Not supplied Φ10mm 4mm (0.16inch) thickness Tightening torque 50Nm Supplied with the compressor Tightening torque 55Nm Included in manifolding kit 5mm (0.2inch) thickness...
  • Page 31: Design Piping

    Scroll compressors, DSH090 to DSH600 | Mechanical connections Design piping General requirements Proper piping practices should be employed to: Ensure adequate oil return, even under minimum load conditions (refrigerant speed, piping slopes…). For validation tests see section Manage oil in the circuit.
  • Page 32 Scroll compressors, DSH090 to DSH600 | Mechanical connections Tandem and trio requirements (Static) Tandem and trio use static oil balancing principle to equalize oil level between the compressors by gravity. This is ensured by a precise suction and oil equalization piping design.
  • Page 33 Scroll compressors, DSH090 to DSH600 | Mechanical connections Trio models with Right suction Compressor 2 Trio models with Left suction Compressor 3 Compressor 1 Tandem models Table 19: Tandem models Outline Tandem Dis‐ Oil equaliza‐ Suction Washer inner di‐ Washer in suction...
  • Page 34 Scroll compressors, DSH090 to DSH600 | Mechanical connections Outline Tandem Dis‐ Oil equaliza‐ Suction Washer inner di‐ Washer in suction Tandem kit Composition Cp1 + Cp2 Suction drawing model charge tion from ameter code number Left 24mm(0.94inch) DSH565X DSH184+DSH381 2"1/8 1"...
  • Page 35 Scroll compressors, DSH090 to DSH600 | Mechanical connections Outline Composition Cp1 + Cp2 Dis‐ Oil equaliza‐ Suction Washer inner di‐ Washer in Trio model Suction drawing Trio kit code +Cp3 charge tion from ameter suction of number Left 33 mm(1.3 inch) Cp2 &...
  • Page 36 Scroll compressors, DSH090 to DSH600 | Mechanical connections To connect the equalization line on rotolock connections, the organ pipe, adaptor sleeves, Teflon gaskets included in the tandem accessory kit must be used. Figure 37: For DSH120, DSH161 or DSH184 Figure 38: DSH240, DSH295 or DSH381...
  • Page 37: Electrical Connections

    DSH090-105-120-140-161-184 (*except DSH140-161 code3, DSH184 code3/7/9) The terminal box is provided with a Ø 25.5mm (φ1 inch) (ISO25) and a Ø 29mm (φ1.14) (PG21) knockouts. Figure 40: Wiring connections for DSH090-105-120-140-161 (*except DSH140-161 code3) Terminal box Ø 29mm (φ1.14inch) knockout Ø...
  • Page 38 Scroll compressors, DSH090 to DSH600 | Electrical connections DSH240-295-381*-485* -600 (*except code 3) The terminal box is provided with 2 triple knockouts and 1 single knockout for power supply and 4 double knockouts for the safety control circuit. The 3 power supply knockouts accommodate the following diameters: •...
  • Page 39: Electrical Specifications

    L1 L2 L3 Thermistor connection Module power N S1 S2 M1 M2 Electrical Specifications Motor voltage Danfoss scroll compressors DSH are available in four different motor voltages as listed below. © Danfoss | Climate Solutions | 2022.10 AB288965961751en-001402 | 39...
  • Page 40 Any compressor damage related to this will not be covered by Danfoss warranty. In the same manner, cables must be selected in a way that ensures the terminal box temperature does not exceed 70°C (158°F).
  • Page 41 Scroll compressors, DSH090 to DSH600 | Electrical connections Table 23: Motor voltage code 4 Max. operating current Winding resistance Compressor model Ω DSH090 1.47 DSH105 1.05 DSH120 1.05 DSH140 0.92 DSH161 0.83 DSH184 0.83 DSH240 0.62 DSH295 0.52 DSH381 0.45 DSH485 0.28...
  • Page 42 Scroll compressors, DSH090 to DSH600 | Electrical connections MOC can be used as a basis for contactors selection. Winding resistance Winding resistance is the resistance between phases at 25°C (77°F) (resistance value +/- 7%). Winding resistance is generally low and it requires adapted tools for precise measurement. Use a digital ohm-meter, a “4 wires” method and measure under stabilised ambient temperature.
  • Page 43 Scroll compressors, DSH090 to DSH600 | Electrical connections Figure 46: PTC Overheat Figure 47: Delay timer active (after PTC over temp.) 40 ms 460 ms 40 ms 460 ms 80 ms 920 ms approx. 1 second While not compulsory, an additional thermal magnetic motor circuit breaker is still advisable for either alarm or manual reset.
  • Page 44 Scroll compressors, DSH090 to DSH600 | Electrical connections Should one of these parameters be incorrect, the relay would lock out (contact M1-M2 open). The red LED on the module will show the following blink code: Figure 49: In case of phase reverse error...
  • Page 45: Application

    Mitigations methods: We can consider two means to reduce compressors sound radiations: Acoustic hoods are quick and easy to install and do not increase the overall size of the compressors. Acoustic hoods are available from Danfoss as accessories. Refer to the tables above for sound levels, attenuation and code numbers.
  • Page 46: Manage Operating Envelope

    Mitigations methods: If an unacceptable level is identified, a discharge muffler with the appropriate resonant volume and mass can be installed. Mitigation Methods To ensure minimum vibrations transmission to the structure, strictly follow Danfoss mounting requirements (mounting feet, rails etc..). For further information on mounting requirements, please refer to section Design compressor mounting.
  • Page 47 No risk of operation beyond the application envelope. No DGT protection required. DSH090 to 184 have no integrated discharge temperature protection, an external protection is required. This external protection device can be a thermostat or a temperature sensor. The discharge gas temperature protection must trip the power supply when it reaches the setting point to protect the compressor from overheating.
  • Page 48: Manage Superheat

    Scroll compressors, DSH090 to DSH600 | Application System evaluation HP and LP must be monitored to respect operating envelope limitation. We consider two types of operating envelope management: Basic and Advanced. Table 28: System evaluation Basic Advanced • HP and LP switch •...
  • Page 49 Scroll compressors, DSH090 to DSH600 | Application Test, criteria and solutions Table 30: Test, criteria and solutions Test Purpose Test condition Pass criteria Solutions Liquid flood Steady-state Suction superheat >5K (9°F) Check expansion valve se- back test and the oil superheat shall not lection and setting.
  • Page 50 12.5 22.5 13.5 Unsafe Area (60 sec max per hour) Evaporating Temperature (°C) CC-000024 Dilution Chart - DSH090 to DSH184 R452B / R454B Figure 55: Dilution Chart (reference at 20°C / 68°F ambient temperature) Evaporating Temperature (°F) 22.5 40.5 17.5 31.5...
  • Page 51: Manage Off Cycle Migration

    Scroll compressors, DSH090 to DSH600 | Application Dilution Chart - DSH240 to DSH600 R410A/ R452B / R454B Figure 56: Dilution Chart (reference at 20°C / 68°F ambient temperature) Evaporating Temperature (°F) 12.5 22.5 Safe Area 13.5 Unsafe Area (60 sec max per hour) Evaporating Temperature (°C)
  • Page 52 The crankcase heaters are designed to protect the compressor against off-cycle migration of refrigerant. For DSH090-105-120-140-161-184, the surface sump heater is located on the compressor shell. For better standby energy consumption, Danfoss provides 48W and 80W two optional surface sump heater. The selection of surface...
  • Page 53 Scroll compressors, DSH090 to DSH600 | Application Charge limits Table 33: Charge limits for single models Refrigerant charge limit Models Composition DSH090 DSH105 DSH120 DSH140 DSH161 DSH184 DSH240 DSH295 DSH381 DSH485 DSH600 Table 34: Charge limits for Tandem models Refrigerant charge limit...
  • Page 54: Power Supply And Electrical Protection

    • HP safety switch, DGT (only for DSH090 to DSH184) and electronic module relay output (M1-M2, only for DSH240 to DSH600) must be wired in the safety chain. Other safety devices such as LP can be either hardware or software managed.
  • Page 55 Scroll compressors, DSH090 to DSH600 | Application Figure 60: Compressor model DSH240-295-381 L1 L3 Figure 61: Compressor model DSH485 (except code 3) and model DSH600 L1 L3 L2 © Danfoss | Climate Solutions | 2022.10 AB288965961751en-001402 | 55...
  • Page 56: Control Logic

    Scroll compressors, DSH090 to DSH600 | Application Figure 62: Compressor model DSH485 code 3 L1 L3 L2 Thermal magnetic motor circuit breaker Compressor motor Control circuit Motor Protection Module Discharge gas thermistor (embedded in com- Phase sequence relay pressor) Thermistor chain (motor and discharge tem-...
  • Page 57 Only for DSH240 to DSH600. Cycle rate limit requirements Danfoss requires a minimum compressor running time of 2 minutes to ensure proper oil return and sufficient motor cooling. Additionally, compressor must not exceed 12 starts per hour. 12 starts per hour must not be considered as an average, this is the maximum number of starts acceptable to keep a good regulation accuracy during low load.
  • Page 58: Reduce Moisture In The System

    • Continuous pump-down: traditional pump-down, Compressor restarts automatically when suction pressure increases up to 4 cycles maximum. Non Return Valve (NRV) DSH090 to DSH600 compressors integrate tight internal non return valve (INRV), therefore no external Non Return Valve (NRV) is needed. Reduce moisture in the system Excessive air and moisture •...
  • Page 59: Assembly Line Procedure

    To achieve this requirement, a properly sized and type of drier is required. Important selection criteria’s include: • driers water content capacity, • system refrigeration capacity, • system refrigerant charge. For new installations of compressors with polyolester oil, Danfoss recommends using the Danfoss DML (100% molecular sieve) solid core filter drier. Assembly line procedure Compressor storage Store the compressor not exposed to rain, corrosive or flammable atmosphere between -35°C (-31°F) and 70°C...
  • Page 60 A2L refrigerants) A typical content of 34% Ag (Silver) is recommended by Danfoss. The use of self-flux alloys (as phosphorous alloys) is not recommended by Danfoss. This type of brazing require a higher working temperature, that may overheat the connectors, damaging the thin layer of copper ,resulting in phosphides creation and joint zone embrittlement.
  • Page 61 Scroll compressors, DSH090 to DSH600 | Application Figure 68: Brazing procedure Heat shield Before eventual un-brazing of the compressor or any system component, the refrigerant charge must be removed and the installation vacuumed (especially with A2L refrigerants). System pressure test and leak detection The compressor has been strength tested and leak proof tested (<3g/year) at the factory.
  • Page 62: Commissioning

    • Phase order: Reverse rotation is obvious if the compressor do not build up pressure and sound level is abnormal high. For DSH090-184 compressors equipped with internal reverse vent valve which can protect compressor without damage within duration below 24h. For more details refer to section Phase sequence and reverse rotation protection.
  • Page 63: Dismantle And Disposal

    If Oil Top-up is needed, it must be done while the compressor is idle. Use the schrader connector or any other accessible connector on the compressor suction line. Always use original Danfoss POE oil 160SZ from new cans. For more detailed information see “Lubricants filling in instructions for Danfoss Commercial Compressors”...
  • Page 64: Packaging

    Scroll compressors, DSH090 to DSH600 | Packaging Packaging Single pack Table 39: Single pack packaging Length Width Height Gross weight Compressor model inch inch inch DSH090 22.2 18.5 28.3 DSH105 22.2 18.5 28.3 DSH120 22.2 18.5 28.3 DSH140 22.2 18.5 28.3...
  • Page 65: Ordering

    Scroll compressors, DSH090 to DSH600 | Ordering Ordering Danfoss scroll compressors DSH can be ordered in either industrial packs or in single packs. Please use the code numbers from below tables for ordering. Compressors DSH090 to DSH184 are delivered with flexible grommets.
  • Page 66: Industrial Pack

    Scroll compressors, DSH090 to DSH600 | Ordering Compressors compatible R410A only Table 42: Single pack compressors compatible R410A only Code no. Compressor model Connections Motor protection 380-415/3/50 208-230/3/60 575/3/60 380-400/3/60 460/3/60 DSH090 Brazed Internal 120H1507 120H1513 120H1515 DSH105 Brazed Internal...
  • Page 67 Scroll compressors, DSH090 to DSH600 | Ordering Code no. Compressor model Connections Motor protection 380-415/3/50 208-230/3/60 575/3/60 380-400/3/60 460/3/60 DSH485 Brazed Module 110-240V 120H1738 120H1361 120H1715 DSH600 Brazed Module 24V AC 120H1789 120H1780 DSH600 Brazed Module 110-240V 120H1785 120H1782 Electronic motor protection, module located in terminal box...
  • Page 68: Accessories And Spare Parts

    Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts Accessories and Spare parts Solder sleeve adapter set Table 45: Solder sleeve adapter set Code no. Description Application Packaging Pack size 120Z0125 Rotolock adaptor set (1"3/4 ~ 1"1/8) , (1"1/4 ~ 7/8")
  • Page 69: Rotolock Nut

    Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts Code no. Description Application Packaging Pack size 8153013 Solder sleeve P07 (1"3/4 Rotolock - 7/8" ODF) Models with 1"3/4 rotolock connection (R410A) Multipack 8153003 Solder sleeve P10 (1"3/4 Rotolock - 1"3/8 ODF) Models with 1"3/4 rotolock connection (R410A)
  • Page 70: Discharge Temperature Protection

    Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts Discharge temperature protection Table 52: Discharge temperature protection Code no. Description Application Packaging Pack size 7750009 Discharge thermostat kit DSH090 to 184 (R410A) Multipack 7973008 Discharge thermostat kit DSH090 to 184 (R410A)
  • Page 71: Acoustic Hoods

    Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts Acoustic hoods Table 56: Acoustic hoods Code no. Description Application Packaging Pack Size 120Z0034 Acoustic hood for scroll compressor DSH090 Single pack 120Z0035 Acoustic hood for scroll compressor DSH105 to 161 (except DSH161-140 code3)
  • Page 72: Trio Kits

    Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts Code no. Description Application Packaging Pack Size 120Z0785 Kit Tandem, Solid,OEL 1”5/8 DSH970E Single pack 120Z0726 Kit Tandem, spacer 30mm DSH895U.DSH1085U (left suction).DSH1200E Single pack 120Z0821 Kit Tandem, spacer 30mm, washer 38mm...
  • Page 73: Updates

    Scroll compressors, DSH090 to DSH600 | Updates Updates Release date Guideline codification number List of changes Reason for change (Year/Month) suction washer position in trio models updated 2022/10 AB288965961751en-001402 2022/06 AB288965961751en-001401 AB288965961751en-001301 © Danfoss | Climate Solutions | 2022.10 AB288965961751en-001402 | 73...
  • Page 74: Online Support

    Online support Danfoss offers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below. The Danfoss Product Store The Danfoss Product Store is your one-stop shop for everything product related—no matter where you are in the world or what area of the cooling industry you work in.

Table of Contents