Configuration
8.5 Configuration control (option handling)
8.5.3.2

Control data record

Operating principle
You define a control data record 196 V1.0, which includes a slot assignment for the
configuration control of an HSC. The control data record can also be read back.
The control data record is only processed with configured configuration control; otherwise it
is rejected.
Rules
Observe the following rules:
● The entry for slot 1 only identifies the PM (see also Table 8-3 Slot assignment
(Page 117)).
● All modules up to the max. possible configuration of the HCS must be registered in
control data record.
● The entries up to at least the last slot of the station master must be contained in the
control data record. Entries beyond the last slot must be pre-assigned with "Module not
available".
● Multiple configured slots may not be assigned to the same actual slot. In other words,
each station option slot may be present only once in the control data record.
● Empty slots are allowed in combined mode.
● Moving modules is not allowed.
118
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006