Causes of errors and possible remedies
Error
code
5104
5105
5106
5107
5109
510B
510E
510F
5110
5113
5114
5115
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
Description
Channel fault: Triac break-
down
"Breakdown" means the triac
is defective and conducts
continuously even without
being activated. For a 100 %
setpoint, the fault can be
neither detected nor flagged.
Channel fault:
Fuse tripped or triac has
high resistance
Return fuse tripped
Channel fault:
Heating element or radiator
wire defective
Switch-off threshold for in-
ternal device temperature
At least one voltage is not
connected
Rotating field error
Phase LX1 is not connected. •
Phase LX3 is not connected.
Channel fault: Partial load
failure
Channel fault: Current load
too high
Phase current LX1 too high
Process and system messages, error handling
11.2 Power Output Module (POM)
Possible causes and solutions
Triac is defective ⇒ Return POM
Switch off machine, check fuse, cabling, heating ele-
ment and rectify fault, restart
Triac is defective => Return POM
Switch off machine, check return fuse, cabling, heating
element and rectify the fault, restart
Switch off machine, check cabling and heating element
and rectify fault, restart
For POM4220 Highend, connection type "phase-phase":
Check incoming fuse
For POM4220 Highend, connection type "2-pin switch-
ing": Check fuse
Trip threshold overshot: The heating is switched off auto-
matically by the device.
Actions:
Check that the fan module is functioning correctly, if
installed
Switch off the machine, rectify the fault (e.g. cooling
malfunction), restart
Check power supply, cabling and, if necessary, connect
the missing voltage
Check power supply, cabling and, if necessary, connect
the missing voltage
Check power supply, cabling and, if necessary, connect
the missing voltage
Configure parameter "Phase LX1 / LX3" as "not con-
nected"
Switch off machine, check cabling and heating elements
and rectify fault, restart
Switch off machine, check cabling and heating elements
and rectify fault, restart
Switch off machine, check cabling and heating elements
and rectify fault, restart