Causes of errors and possible remedies
Error
code
5104
5105
5106
5107
5109
510B
510E
510F
5110
5113
5114
5115
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
Description
Channel fault: Triac break-
down
"Breakdown" means the triac
is defective and conducts
continuously even without
being activated. For a 100 %
setpoint, the fault can be
neither detected nor flagged.
Channel fault:
Fuse tripped or triac has
high resistance
Return fuse tripped
Channel fault:
Heating element or radiator
wire defective
Switch-off threshold for in-
ternal device temperature
At least one voltage is not
connected
Rotating field error
Phase LX1 is not connected. •
Phase LX3 is not connected.
Channel fault: Partial load
failure
Channel fault: Current load
too high
Phase current LX1 too high
Process and system messages, error handling
11.2 Power Output Module (POM)
Possible causes and solutions
Triac is defective ⇒ Return POM
•
Switch off machine, check fuse, cabling, heating ele-
•
ment and rectify fault, restart
Triac is defective => Return POM
•
Switch off machine, check return fuse, cabling, heating
•
element and rectify the fault, restart
Switch off machine, check cabling and heating element
•
and rectify fault, restart
For POM4220 Highend, connection type "phase-phase":
•
Check incoming fuse
For POM4220 Highend, connection type "2-pin switch-
•
ing": Check fuse
Trip threshold overshot: The heating is switched off auto-
matically by the device.
Actions:
Check that the fan module is functioning correctly, if
•
installed
Switch off the machine, rectify the fault (e.g. cooling
•
malfunction), restart
Check power supply, cabling and, if necessary, connect
•
the missing voltage
Check power supply, cabling and, if necessary, connect
•
the missing voltage
Check power supply, cabling and, if necessary, connect
the missing voltage
Configure parameter "Phase LX1 / LX3" as "not con-
•
nected"
Switch off machine, check cabling and heating elements
•
and rectify fault, restart
Switch off machine, check cabling and heating elements
•
and rectify fault, restart
Switch off machine, check cabling and heating elements
•
and rectify fault, restart
181