Technical specifications
13.2 Technical Specifications CIM4210
Article number
Interfaces
Interfaces/bus type
PROFIBUS DP
Transmission rate, max.
•
Design of electrical connection of
•
PROFIBUS interface
Supports protocol for PROFINET IO
Transmission rate, max.
•
Design of electrical connection of
•
PROFINET interface
Protocols
Supports protocol for PROFINET IO
PROFIBUS DP
Further protocols
EtherNet/IP
•
Interrupts/diagnostics/status information
Number of status displays
LED status display
Isolation
Overvoltage category
Degree of pollution
EMC
EMC interference emission
Electrostatic discharge acc. to IEC
61000-4-2
Field-related interference acc. to IEC
61000-4-3
Conducted interference due to burst
acc. to IEC 61000-4-4
Conducted interference due to surge
acc. to IEC 61000-4-5
Conducted interference due to high-
frequency radiation acc. to IEC 61000-
4-6
Degree and class of protection
IP degree of protection
208
6BK1942-1AA00-0AA0
PROFINET IO
100 Mbit/s
2x RJ45
Yes
No
No
3
LED green = ready, LED yellow = heating on/off, LED
red = error display
III
2
Limit value in accordance with IEC 61000-6-4:2007 +
A1:2011
4 kV contact discharging, 8 kV air discharging
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m
(2.0 ... 2.7 GHz)
2 kV power supply lines, 2
kV PROFINET cables
DC supply lines: 0.5 kV
symmetric and unsymmet-
ric PROFINET cables: 1 kV
unsymmetric
10 V (0.15 ... 80 MHz)
IP20
6BK1942-1BA00-0AA0
PROFIBUS DP
12 Mbit/s
9-pin sub D socket
No
Yes
2 kV power supply lines / 2
kV PROFIBUS cables
DC supply lines: 0.5 kV
symmetrical and asymmet-
rical, PROFIBUS lines: 1
kV asymmetrical
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006