Siemens SIPLUS HCS Series Operating Instructions Manual page 239

Io systems for heating elements. heating control system
Hide thumbs Also See for SIPLUS HCS Series:
Table of Contents

Advertisement

Article number
Standards, approvals, certificates
Reference designation according to DIN EN
81346-2
Ambient conditions
Ambient temperature during operation
min.
max.
Ambient temperature during stor-
age/transportation
Storage, min.
Storage, max.
Transportation, min.
Transportation, max.
Air pressure acc. to IEC 60068-2-13
Operation, min.
Operation, max.
Storage, min.
Storage, max.
Altitude during operation relating to sea level
Installation altitude above sea level, max.
Relative humidity
Operation at 25 ℃, max.
Operation at 50 ℃, max.
Vibrations
Vibration resistance during operation acc.
to IEC 60068-2-6
Vibration resistance during storage acc. to
IEC 60068-2-6
Shock testing
Shock resistance during operation acc. to
IEC 60068-2-27
Shock resistance during storage acc. to
IEC 60068-2-29
Dimensions
Width
Height
Depth
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
13.5 Technical specifications for I/O module
6BK1900-0BA00-0AA0
K
0 °C
55 °C
-25 °C
70 °C
-25 °C
70 °C
860 hPa
1 080 hPa
660 hPa
1 080 hPa
2 000 m
95 %
50 %; 95 % at 25 °C, decreasing linearly to 50 %
at 50 °C
10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1 g
5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1 g
15 g / 11 ms / 3 shocks/axis
25 g / 6 ms / 1 000 shocks/axis
27 mm
141 mm
110 mm
Technical specifications
237

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siplus hcs4200 profinetSiplus hcs4200 profibus dp

Table of Contents