OutputCodeDefinition
PTS
PowerThresholdExceeded(LoadShedding2):
This output signal is linked to the kva ratings as configured in the
Power Level settings menu. When the power drawn by the load
exceeds the threshold levels set output PTS will be activated so as to
load shed selected loads.
BatteryChargeOutputsignal:
EES
This output will be activated when the maximum reset timer EET
elapses. This output may be used with a battery charger that will be
switched on depending on the Genset idle time. Output EES will be
deactivated when the battery charge run timer (EDT) elapses.
COP
ControllerAvailable
This output is activated when the ATS controller of the ATyS p is
considered to be operational and ready to switch positions.
Product in Manual Mode
MAN
This output is activated when the product is in Manual Mode (Selector
in MAN position).
Note:
The Engine Exerciser settings are only accessible through Webserver and through Easy Config programming software.
Refer to the Easy Config section for details.
98
EN
AdjustmentRange M-G M-M
NO / NC
NO / NC
NO / NC
NO / NC
ATYS p - 542001E - SOCOMEC