socomec ATyS s Instruction Manual page 113

Automatic transfer switching equipment
Hide thumbs Also See for ATyS s:
Table of Contents

Advertisement

AnnexeII-16.Usercommands
Function 6 Codes
Dec.
Hex.
Words
Address
Address
count
21840
5550
1
21841
5551
1
21842
5552
1
21843
5553
1
21844
5554
1
AnnexeII-17.Setuptimer
Function 3, 6 and 16 Codes
Dec.
Hex.
Words
Address
Address
count
Source1timers
22016
5600
1
22017
5601
1
Source2timers
22023
5607
1
22024
5608
1
22025
5609
1
22027
560B
1
22028
560C
1
22029
560D
1
Generaltimers
22030
560E
1
22031
560F
1
22032
5610
1
ATYS p - 542001E - SOCOMEC
Description
Auto configuration request
1: make autoconfig
Settings backup
1: save current settings as user defaults
2: restore user defaults settings
3: restore factory settings
Source 1 partial counters erase
0x01: Ea+
0x02: Er+
0x04: Es
0x08: Ea-
0x10: Er-
0x20: Hour counter
Source 2 partial counters erase
0x01: Ea+
0x02: Er+
0x04: Es
0x08: Ea-
0x10: Er-
0x20: Hour counter
Product user counters erase
0x01: Genset start counter erase
0x02: Genset runtime counter erase
0x04: Secondary source presence counter erase
0x08: Secondary source active duration counter erase
0x10: Source 1 load supplied duration counter erase
0x20: Source 2 load supplied duration counter erase
Description
1FT: Primary Source fail timer
1RT: Primary Source availability/stabilization timer
2FT: Secondary Source fail timer
2RT/2AT: Secondary Source availability/stabilization timer
2CT: Secondary Source maintain request timer (cooldown timer)
2ST: Secondary Source wait for start timer
EET: Secondary Source engine exerciser timeout
EDT: Secondary Source engine exerciser duration
ODT: Dead band timer
Limit_TON: Test on load is limited
0: unlimited
1: limited
TOT: Test on load duration timer
Unit
Unit
sec.
sec.
sec.
sec.
sec.
sec.
hours
sec.
sec.
sec.
EN
113