12.3. Priority source loss and restoration sequence M-M
Stable position in M-M applications
Configuration
• APP = M-M: Network - Network application
• priority source available
• emergency source not available
• switch in position i
Priority source lost?
no
end 1ft?
no
end 2Rt?
yes
transfer i --> 0
end Odt?
no
transfer 0 --> ii
• priority source unavailable
• emergency source available
• switch in position ii
12.4. Prioritysourceautomaticrestorationsequence
This sequence is started as soon as the system is in AUTO mode and in position II. Specific function Automatic
retransfer inhibited: Once source 1 is restored, it may be preferable not to retransfer the load from source 2 to source
1 immediately. Once the retransfer from source 2 to source 1 is possible, the RETRANS function locks the retransfer,
and the AUT LED flashes pending the operator's confirmation.
The VALIDATION key must be pressed or an input must be programmed on RTC to authorise the retransfer.
62
EN
no
yes
• priority source loss
sequence
yes
• priority source unavailable
• emergency source available
• switch in position ii
Priority source
present?
no
yes
no
emergency source
present?
yes
no
end 1Rt?
yes
yes
no
Priority source
present?
• priority source available
• emergency source unavailable
• switch in position i
end dyn.
1Rt. ?
yes
transfer ii --> 0
end Odt?
yes
transfer 0 --> i
ATYS p - 542001E - SOCOMEC