socomec ATyS s Instruction Manual page 96

Automatic transfer switching equipment
Hide thumbs Also See for ATyS s:
Table of Contents

Advertisement

INPUTCodeDefinition
CHP
Changeofposition
Once this input is active the automatism is inhibited and the product
transfers on the opposite solution (From I to II and from II to I). If
the product is in 0 when the input is activated then the automatism
is inhibited, but the product won't transfer. When the input is
desactivated the product goes back in Automatic mode.
AnnexeI-11.2.OperationoftheEONfunction:
E2T when set as Limited
eOn input
Operation request
"starting order"
contact
Pos II
Pos I
E2T takes priority over EON if E2T is set as LIM (Limited)
eOn input
Operation request
"starting order"
contact
Pos II
Pos I
96
EN
e1t
e2t
starting time
?
e1t
e2t
starting time
?
2at
AdjustmentRange
NO / NC
e3t
e3t
M-G M-M
2Ct
2Ct
ATYS p - 542001E - SOCOMEC