7.3.2.3. ATyS p (optional module) input / output Wiring connections
The ATyS  p can accept a total of 4 plug in I/O modules. (Attn: If using a communication module the total slots
available for extension I/O modules may be reduced to a maximum of 3 with MODBUS RTU and 2 with the Ethernet
module installed).
Inputs
7.3.2.4. Terminal denomination, description and characteristics.
Denomination Terminal Description
Output
04
Contacts
13
(Motorisation
14
Module)
24
63A
64A
ATS Output
63B
Contact
64B
GensetStart/
71
StopSignal
72
74
AdditionalAux
81
Contact
82
84
Included with
2000 A to
91
3200 A
92
94
ATS Power
101 - L/N
supply Input I
102 - N/L
ATSVoltage
103 - 7/8
SensingInput*
104 - 5/6
Switch I
105 - 3/4
106 - 1/2
ATS Power
201 - L/N
supply Input II
202 - N/L
ATYS p - 542001E - SOCOMEC
Outputs
Aux Contact Position 0 - Normally Open Contact
Common for Aux Contacts positions I - 0 - II
Aux Contact position I: Normally Open Contact
Aux Contact position II: Normally Open Contact
Motorisation module available output. Closed
when the ATyS p is in Auto mode and motorisation
is operational. (No Fault powered and ready to
changeover)
Programmable output dry contacts. (By default
set as POP à ATS control module available output,
closed when the ATyS p is in Auto mode and ATS
is operational. (No Fault, powered and ready for a
changeover sequence)
Signal to Start / Stop the Genset: Common for 72 & 74
Signal to Start / Stop the Genset: NC contact. (71/72)
Signal to Start / Stop the Genset: NO contact. (71/74)
Common for Aux Contacts positions I
Aux Contact position I: Normally Closed Contact
Aux Contact position I: Normally Open Contact
Common for Aux Contacts positions II
Aux Contact position II: Normally Closed Contact
Aux Contact position II: Normally Open Contact
Power supply I – L/N
Power supply I – N/L
Phase or neutral connected on power contact 7 or 8
of Switch I
Phase connected on power contact 5 or 6 of Switch
I
Phase connected on power contact 3 or 4 of Switch
I
Phase or neutral connected on power contact 1 or 2
of Switch I
Power supply II – L/N
Power supply II – N/L
In13
In14
In11
In12
In9
I
I
I
I
I
I
I
I
I
14
13
24
23
14
13
24
23
14
O
O
O
O
O
O
O
O
O
24
23
14
13
24
23
14
13
24
Out9
Out8
Out7
Out6
Out5
4
3
Characteristics Recommended
Dry Contacts
2 A AC1 / 250V
2A / 24VDC
Dry Contacts 2 A
AC1 / 250V
Dry Contacts 2 A
AC1 / 250V
Dry Contacts 2 A
AC1 / 250V
208 - 277VAC ± 20% :
50/60Hz
575 VAC
(ph-ph) max
332Vac
(ph-n) max
208 - 277VAC ± 20% :
50/60Hz
In10
In7
In8
I
I
I
I
I
I
I
13
24
23
14
13
24
23
O
O
O
O
O
O
O
23
14
13
24
23
14
13
Out4
Out3
Out2
2
1
Cable Section
1.5 – 2.5 mm
2
1.5 – 2.5 mm
2
1.5 – 2.5 mm
2
1.5 – 2.5 mm
2
1.5 – 2.5 mm
2
1.5 – 2.5 mm
2
1.5 – 2.5 mm
2
EN
43

Hide quick links: