STEP 1
Installation
Caution:
Recommended
Ensure that the
orientation
product is installed on
a flat rigid surface.
138
20
Door cut-out for
front panel.
ATyS p 800 to 1000 A
ATyS p 1250 A
16 x 11
ø 9
ø 15
15.75
28.5
15.75
8.5
33
8.5
60
50
Example: Control wiring for a 400VAC application having a 3 phase and neutral supply.
2
R1 R2 S1 S2 T1 T2
312 313 314 315 316 317
5
4 3 2 1
ATYS p - 542001E - SOCOMEC
Ok
Ok
ATyS p 1600 to 3200 A
ø12.5
5
5
M
25
25
30
30
T
45
45
90
C
STEP 2
Minimum cable section Cu (mm
(IEC 60947-1)
Recommended cable section Cu (mm
Maximum cable section Cu (mm
Maximum Cu busbar width (mm)
Type of screw
Recommended tightening torque (N.m)
Maximum tightening torque (N.m)
LOAD
ATyS D20
Remote Control /
6
Display Unit
7
8 9
63A 64A 24 14 04 13
M
51,5
T
M
51.5
T
800 A
1000 A
1250 A
3 P
4 P
3 P
4 P
3 P
4 P
255
335
255
335
255
335
80
80
80
80
80
80
391
391
391
391
391
391
Power Terminal Connections
To be connected using terminal lugs, rigid or flexable busbars.
FRAME B6
800 A
1000 A
) at Ith
2
2x185
-
) at Ith
2x50x5
2x60x5
2
)
2x300
4x185
2
63
63
M8
M8
8.3
8.3
13
13
STEP 3
CONTROL / COMMAND Terminals
Ensure that the product is in Manual Mode.
1
1
2
preferred source
alternate source
1. Position 0 order
2. Position 1 order
3. Position 2 order
4. Zero position priority order
5. Remote Control Enable (Priority over Auto)
6. Product Available output (Motor)
7. Position II aux contact
8. Position I aux contact
9. Position 0 aux contact
10. O/P to ATyS D20 remote unit
11. Programmable Output Contact.
By default set to ATS Product
Available - Normally Open
ATyS p 800 to 1600 A
C
21
ATyS p 2000 to 3200 A
C
1600 A
2000 A
2500 A
3 P
4 P
3 P
4 P
3 P
4 P
347
467
347
467
347
467
120
120
120
120
120
120
391
391
523
523
523
523
FRAME B7
FRAME B8
1250 A
1600 A
2000 A
2500 A
-
-
-
-
2x60x7
2x100x5
3x100x5
4x100x5
4x185
6x185
-
-
63
100
100
100
M10
M12
M12
M12
20
40
40
40
26
45
45
45
12-15. Programmable Inputs 1-4
16-17. Programmable Inputs 5-6
18. Aux. Supply (207/210) to be used
with ATyS optional I/O modules
19. Contact "Start/Stop Genset" : if S1
is not available the NC contact le
contact (71-72) is close
20. Contact "Start/Stop Genset" : if S1
is not available the NO contact le
contact (71-74) is open
21. Option Module Slots 1 to 4
22. Current Transformer incoming cable
connections
23. Voltage Sensing Inputs
24. Power Supply Inputs
Dimensions
in mm.
21
3200 A
3 P
4 P
347
467
120
120
523
523
3200 A
-
3x100x10
-
100
M12
40
45
1
2
EN