socomec ATyS s Instruction Manual page 133

Automatic transfer switching equipment
Hide thumbs Also See for ATyS s:
Table of Contents

Advertisement

Dec.
Hex.
Words
Address
Address
count
23892
5D54
1
23893
5D55
1
23894
5D56
1
23895
5D57
1
23896
5D58
1
23897
5D59
1
23898
5D5A
1
23899
5D5B
1
23900
5D5C
1
ATYS p - 542001E - SOCOMEC
Description
OUT 2 pulse output value
0: 0,1 kWh/kvarh
1: 1 kWh/kvarh
2: 10 kWh/kvarh
3: 100 kWh/kvarh
4: 1000 kWh/kvarh
5: 10000 kWh/kvarh
OUT 2 pulse output duration
0: 100ms
1: 200ms
2: 300ms
3: 400ms
4: 500ms
5: 600ms
6: 700ms
7: 800ms
8: 900ms
Type of analog output OUT 1
0: 0/20 mA
1: 4/20 mA
2: 30 V
Output allocation analog OUT1
0: U12 (V)
1: U23 (V)
2: U31 (V)
3: V1 (V)
4: V2 (V)
5: V3 (V)
6: I1 (A)
7: I2 (A)
8: I3 (A)
9: In (A)
10: F (Hz)
11: ∑P (W)
12: ∑Q (var)
13: ∑S (VA)
14: ∑PFL (%)
15: ∑PFC (%)
Value at 0 or 4 mA from analog output OUT 1
(-20000 to +20000)
Unit at 0 or 4 mA from analog output OUT1
0: /
1: k
2: M
Value at 20 mA from analog output OUT 1
(-20000 to +20000)
Unit at 20 mA from analog output OUT1
0: /
1: k
2: M
Type of analog output OUT 2
0: 0/20 mA
1: 4/20 mA
2: 30 V
Unit
-
-
EN
133