socomec ATyS s Instruction Manual page 44

Automatic transfer switching equipment
Hide thumbs Also See for ATyS s:
Table of Contents

Advertisement

Denomination Terminal Description
ATSVoltage
SensingInput*
Switch II
ATS Module
Programmable
Inputs
Motorisation
Module
Control Inputs
ATS Module
Programmable
Inputs
RemoteInterface
I/OExtension
Modules
2xInput
2xOutput
(Optional)
MODBUS
Module
(Optional)
Current
transformers*
*For metering and sensing details, please refer to page 40.
CautIOn
44
EN
203 - 1/2
Phase or neutral connected on power contact 1 or 2
of Switch II
204 - 3/4
Phase connected on power contact 3 or 4 of Switch II
205 - 5/6
Phase connected on power contact 5 or 6 of Switch II
206 - 7/8
Phase or neutral connected on power contact 7 or 8
of Switch II
207 -
Common control terminal for inputs 5 & 6,
208 – 209 and negative for optional module
extension I/O supply
208
Programmable Input number 5
209
Programmable Input number 6
210 +
+ dc Power supply for optional module
extension I/O supply
312
Remote Control Mode Enable when closed with 317
313
Position 0 order if closed with 317. (Priority order input
forcing the product to remote control mode and 0 position)
314
Position II order if closed with 317
315
Position I order if closed with 317
316
Position 0 order if closed with 317
317
Common control terminal for 312 - 316 ATyS
(Specific Voltage Supply)
413
Programmable Input number 1
414
Programmable Input number 2
415
Programmable Input number 3
416
Programmable Input number 4
417
Common supply for programmable inputs 1 to 4 (413 - 416)
RJ
Output to D20 remote control & display module
I 13+
Programmable Input
I 14 -
I 23 +
Programmable Input
I 24 -
O 13
Programmable Output
O 14
O 23
Programmable Output
O 24
0
RS 485 MODBUS Communication module terminals
-
+
Current Transformer:- I1
R1
R2
Current Transformer:- I2
S1
S2
Current Transformer:- I3
T1
T2
do not connect terminals 312 to 317, 413 to 417 or 207 to 209 to any power
supply. these order inputs are powered through terminal 207
(317 or 417 respectively) and external dry contacts only.
Characteristics Recommended
Cable Section
575 Vac
(ph-ph) max
1.5 – 2.5 mm
332Vac
(ph-n) max
Attn:
To be used with
dry contacts fed
1.5 – 2.5 mm
from 207 ONLY.
To Ext I/O Only
Attn:
Do not connect to
any Power supply
1.5 – 2.5 mm
Max cable
length 100m
Do not connect to
any power supply.
Attn:
1.5 – 2.5 mm
To be used with
dry contacts fed
from 417 ONLY.
Up to 3m
RJ 45
To be powered
from terminals
207 – 210
1.5 – 2.5 mm
10 – 30 VDC
Dry Contacts 2 A
1.5 – 2.5 mm
AC1 / 250V
CT Input
1.5 mm²
2 A or 1 A
ATYS p - 542001E - SOCOMEC