socomec ATyS s Instruction Manual page 136

Automatic transfer switching equipment
Hide thumbs Also See for ATyS s:
Table of Contents

Advertisement

AnnexeII-28.1.Detailledevents
Function 6 and 16 Codes
• Command Zone R1
NOTE: When zone R1 is completed with value 1, zone R2 automatically fils in with the last saved value. At the end
of this operation, writing 0xFFFE in zone R1 enables the reading of the next data.
Dec.
Hex.
Address
Address
24320
5F00
24321
5F01
Function 3 Codes
• Data Zone R2
Dec.
Hex.
Address
Address
24336
5F10
24337
5F11
136
EN
Words
Description
count
1
Action
0x0001: Reset read pointer
0xFFFE: Get next data
1
Filtering action - If not written, no filtering is done
To use filtering, entire table should be written in one time with
function 16
0x00XX: only get events in the form XXyy
0xFFFF: no filter
Words
Description
count
1
record count
If record count == 0xFFFF, it means that filtering process is not
done now, so the reader has to re-read the table to get the
values.
1
record size
If record size == 0xFFFF, it means that filtering process is not
done now, so the reader has to re-read the table to get the
values.
120
8 * Event data record
Unit
Unit
nb words
ATYS p - 542001E - SOCOMEC