socomec ATyS s Instruction Manual page 48

Automatic transfer switching equipment
Hide thumbs Also See for ATyS s:
Table of Contents

Advertisement

7.4.4. PrioritysourceconnectedonswitchIorII(M-GApplication)
Certain applications or installation constraints may require that the main supply is connected to switch II instead of
switch I. This is possible to cater for with certain precautions.
The ATyS p includes the facility to adapt the switch priority supply using the configuration in the software that will swap
the main supply and switch logic (S1 = SW2 in SETUP Menu). When this is done pay attention to the LED switch
position display that will no longer correspond to the identification labels on the switch. The LED's will correspond to
the switch that is energized however the main supply will be displayed under II. In this case it is important to update
the ATS controller sticker so as to correspond with the actual wiring and configuration.
Changefrom:
to:
CautIOn
BOTTOM:SOURCECABLEENTRY
switch II
Red wires
48
EN
when reversing the switch priority (main supply connected to switch ii) update
the Led numbering on the front of the ats to correspond with the actual wiring,
configuration and Led indication.
inverse (i – ii -> ii – i)
switch I
Black wires
Black wires
Source1onswitchI:
Standard configuration.
Source1onswitchII:
Set parameter S1=SW2 at
YES, in SETUP menu
S1=SW2
TOP:SOURCECABLEENTRY
switch II
ATYS p - 542001E - SOCOMEC
YES
switch I
Red wires

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Atys sdAtys rAtys dAtys tAtys gAtys p