6.3.5. Incomingcopperbarconnectionkitassembly
2000A–2500A(MinimumCubarsectionforIth2000A3x100x5mm;andforIth2500A4x100x5mm)
VerSion 01
Direct
Connection
3200A(MinimumCubarsection3x100x10mm)
VerSion 04
A
B
6.3.6. Outgoingbridgeconnectionassembly
2000A–2500A(MinimumCubarsectionforIth2000A3x100x5mm;forIth2500A4x100x5mm)
VerSion 07
3200A(MinimumCubarsection3x100x10mm)
VerSion 10
!
2900AMax
ATYS p - 542001E - SOCOMEC
VerSion 02
VerSion 05
B
A
VerSion 08
VerSion 11
VerSion 03
VerSion 06
!
2900AMax
VerSion 09
VerSion 12
V2 & V3
Kit :
2619 1200 x 1
2629 1200 x 1
2639 1200 x 1
Connection
bar 2619 1200
included with
3200A
V4
Kit :
2699 1200 x 1
V5 & V6
Kit :
2629 1200 x 1
2639 1200 x 1
V7 & V8
Kit :
2619 1200 x 2
2699 1201 x 2
2629 1200 x 1
4109 0320 x 1
V9
Kit :
2619 1200 x 2
2629 1200 x 2
2639 1200 x 2
Connection
bar 2619 1200
included with
3200A
V10 & V11
Kit :
2699 1201 x 2
2629 1200 x 1
4109 0320 x 1
V12
Kit :
2629 1200 x 2
2639 1200 x 2