socomec ATyS g Quick Start

socomec ATyS g Quick Start

Motorised source changeover switch, automatic transfer switching equipment
Hide thumbs Also See for ATyS g:

Advertisement

Quick Links

549669C
QUICK START
125 A - 630 A
EN
ATyS
g
Motorised Source Changeover Switch
Automatic Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
- Packaging and contents are in good condition
- The product reference corresponds to the order
- Contents should include:
Qty 1 x ATyS g
Qty 1 x Emergency handle and fixing clip
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
• This product must always be installed and
commissioned by qualified and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables connected to
the product when voltage may be, or may become
present on the product, directly through the mains or
indirectly through external circuits.
• Always use an appropriate voltage detection device to
confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
- For 125 - 160 A (Uimp = 8 kV). Terminations must respect
a minimum of 8 mm clearance from live parts to parts
intended to be earthed and between poles.
- For 200 - 630 A (Uimp = 12 kV). Terminations must respect
a minimum of 14 mm clearance from live parts to parts
intended to be earthed and between poles.
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
In case the product is dropped or damaged in any way it is
recommended to replace the complete product.
Accessories
• Bridging bars and connection kits.
• Control voltage transformer (400 VAC
• DC power supply (12/24 VDC
230 VAC).
• Phase barriers.
• Terminal shrouds.
• Terminal screens.
• Auxiliary contacts (Additional).
• Padlocking in 3 positions (I - O - II).
• Lockout accessories (RONIS - EL 11 AP).
• Door escutcheon frame.
• ATyS D10 Interface (remote display).
• Voltage sensing kit.
• Sealable cover.
• RJ45 cable for ATyS D10.
• Plug-in optional Modbus RS485 communication module.
For further details refer to the product instruction manual
under chapter "Spares and Accessories".
www.socomec.com
To download, brochures, catalogues
and technical manuals:
https://www.socomec.com/range-
automatic-transfer-switches_
en.html?product=/atys-t-atys-g_
en.html
Installation and Commissioning
STEP 1
Cabinet / Back
Plate Installation
STEP 1
1
Max.
0.51 in.
13 mm.
Mounting
3
230 VAC).
125 A to 400 A.
STEP 2
To be connected using terminal lugs, rigid or flexable
busbars.
Minimum cable section Cu (mm²)
Recommended Cu busbar cross-section (mm²)
Maximum Cu cable cross-section (mm²)
Maximum Cu busbar width (mm)
Type of screw
Recommended tightening torque (lb.in/N.m)
Maximum tightening torque (lb.in/N.m)
STEP 2
STEP 3
Power Terminal
COMMAND /
Power SUPPLY and
Connections
CONTROL
ATS Controller
terminal
connections
Clip for
storage of
the
emergency
handle
Installation
Caution: ensure
that the product
is installed on a
flat rigid surface.
500 A, 630 A.
Power Terminal Connections
125 A
35
50
25
M8
73.46/8.3 73.46/8.3 73.46/8.3 177.02 /20 177.02 /20 177.02 /20 354.04/40 354.04/40
115.06/13 115.06/13 115.06/13 230.13/26 230.13/26 230.13/26 398.30/45 398.30/45
STEP 4
STEP 5
STEP 6
CHECK
PROGRAMMING
Terminal
Connections
2
M8 Type Z
M8
Recommended
orientation
Removing covers
FRAME B3
FRAME B4
160 A
200 A
250 A
315 A
35
50
95
120
-
-
-
-
95
120
150
240
25
25
32
M8
M8
M10
M10
STEP 7A
AUT Mode
(Automatic Control)
STEP 7B
AUT Mode
(Remote Control)
STEP 7C
Manual Mode
STEP 7D
Padlocking Mode
OK
OK
FRAME B5
400 A
500 A
630 A
185
2x95
2x120
-
-
2x32x5
2x40x5
240
2x185
2x300
32
32
50
50
M10
M12
M12

Advertisement

loading

Summary of Contents for socomec ATyS g

  • Page 1 - The product reference corresponds to the order emergency - Contents should include: handle Qty 1 x ATyS g Qty 1 x Emergency handle and fixing clip Quick Start instruction sheet Warning Risk of electrocution, burns or injury to persons and / or damage to equipment.
  • Page 2 Parity: None MODBUS module is to be installed in one of the slots provided in the ATyS g ATS control unit. Easy Config may be installed on a PC connected through MODBUS module for a direct ATyS configuration, Whilst in manual mode, check the wiring and if ok power up the either isolated with possibility to create a specific configuration for a product.
  • Page 3 It is imperative that the network supply is available and that the READY wiring to the ATyS g voltage sensing terminals 103 – 106 and 203 – 206 has been done. It is TEST OFF LOAD...
  • Page 4 1.30 1.30 Non contractual document. CORPORATE HQ CONTACT: SOCOMEC SAS 1-4 RUE DE WESTHOUSE - 67235 BENFELD, FRANCE - WWW.SOCOMEC.COM CORPORATE HQ CONTACT: SOCOMEC SAS 1-4 RUE DE WESTHOUSE - 67235 BENFELD, FRANCE - WWW.SOCOMEC.COM Subject to change without notice.