socomec ATyS s Instruction Manual page 87

Automatic transfer switching equipment
Hide thumbs Also See for ATyS s:
Table of Contents

Advertisement

1
SETUP
CT SEC
5
S1=SW2
NO
BACKLGHT
INT
CODE P
1000
CODE E
0000
BACKUP
SAVE
AnnexeI-6.1.**Phaserotationcheck:
This functionality checks the consistency of phase rotation i.e. of the wiring prior to commissioning.
Example: If the parameter ROT PH = ABC:
L1 (A)
L3 (C)
Display
1
2
(Rotation check on sources
WaRnIng
ATYS p - 542001E - SOCOMEC
Definition
Current Transformer secondary rating
Inverted power section switch wiring. Switch
1 (Front) cabled as Switch 2 and Switch 2
(Back) cabled as Switch 1.
NO: Not Inverted
YES: Inverted
The LCD backlight may be set to:
OFF: Always Off
ON: Always On
INT: On after pressing the keypad and during
operating sequences only. (Turned off after 2
minutes of inactivity).
Password Code to modify and save settings
in Programming Mode.
Default factory setting: 1000
Password Code to modify and save settings
in Operating Mode.
Default factory setting: 0000
Save the settings in the backup so as to recall
them later within the same menu.
Load to charge the backup data
OK
L2 (B)
or
1
2
1
2
and
).
function available on both sources in case of 4nBL/4BL or 3nBL/3BL type of
network and only on source
AdjustmentRange
1 A
2 A
NO
YES
OFF
ON
INT
0000 to 9999
0000 to 9999
SAVE
LOAD
L1 (A)
L2 (B)
depending on the non-compliant source
1
in case of 41nBL or 42nBL network.
M-G M-M
NON OK
L3 (C)
EN
87