Download Print this page
socomec ATYS P Quick Start Manual

socomec ATYS P Quick Start Manual

800a-3200a motorised source changeover switch
Hide thumbs Also See for ATYS P:

Advertisement

Installation and Commissioning
QUICK START
800A - 3200A
EN
ATyS
p
STEP 1
Cabinet / Back
Plate Installation
Motorised Source Changeover Switch
Automatic Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
Qty 1 x ATyS p
Qty 1 x Emergency handle and fixing clip
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
• This product must always be installed and
commissioned by qualified and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables connected to
the product when voltage may be, or may become
present on the product, directly through the mains or
indirectly through external circuits.
• Always use an appropriate voltage detection device to
confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
• In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
STEP 4
• Bridging bars and connection kits.
• Control voltage transformer (400Vac -> 230Vac).
• DC power supply (12/24Vdc -> 230Vac).
• Mounting spacers to raise the product x 10mm.
• Phase barriers.
• Terminal shrouds / Terminal screens.
• Auxiliary contacts (Additional).
• Padlocking in 3 positions (I - O - II).
• Lockout accessories (RONIS - EL 11 AP).
• Door escutcheon frame.
• ATyS D20 Interface (remote control / display unit).
• RJ45 cable for ATyS D20 => ATyS p.
• Voltage sensing kit.
• Current transformers.
• Plug-in optional modules: RS485 MODBUS
communication, 2 inputs/2 outputs, Ethernet
communication, Ethernet communication + RS485
JBUS/MODBUS gateway, Analogue outputs, Pulse
outputs.
For further details refer to the product instruction manual
under chapter "Spares and Accessories"
www.socomec.com
To download, brochures, catalogues and technical manuals:
ATyS t
ATyS t
ATyS g
ATS CONTROLLER
ATS CONTROLLER
ATS CONTROLLER
Dual auxiliary supply:
Dual auxiliary supply:
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Uc 208-277V~ +/-20% 50/60Hz
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
Power comsumption: 22VA
Power comsumption: 22VA
See instruction sheet
See instruction sheet
See instruction sheet
Printing informations: 1 color Black. White paper 90g/m
.
2
Printing size: 420x297. Final size 210x297. This page visible first.
Non contractual document.
542 000 E - 09/15 - EN
Subject to change without notice.
STEP 2
STEP 3
STEP 4
STEP 5
Power Terminal
COMMAND /
Power SUPPLY and
CHECK
Connections
CONTROL terminal
ATS Controller
connections
Terminal
Connections
Clip for
storage of
the
emergency
handle
Power Supply, Sensing and Control wiring (ATS Controller)
Connect the product with a cable of section of 1,5 to 2,5 mm
.
2
Screw M3 - Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm
ATS Power Supply
Input II
Power supply II - L
Power supply II - N
208-277 VAC ±20%:
50/60 Hz
ATS Voltage Sensing
Input
Source supply II
S II - Phase 1
S II - Phase 2
S II - Phase 3
600 VAC (ph-ph) max
S II - Neutral
Current Transformer
332 VAC (ph-n) max
incoming cable connections
Programmable Inputs
Programmable Inputs
To opt. Module/Common
To opt. Module/Common
Progr. Inputs (208-209)
Progr. Inputs (208-209)
To opt. Module positive
To opt. Module positive
ATyS g
Slots for optional modules
ATyS p
See on the back "Optional modules"
ATS CONTROLLER
ATS CONTROLLER
Dual auxiliary supply:
Dual auxiliary supply:
Uc 208-277V~ +/-20% 50/60Hz
Uc 208-277V~ +/-20% 50/60Hz
Genset
Power comsumption: 22VA
Power comsumption: 22VA
Start/Stop Signal
Start/Stop Signal
See instruction sheet
See instruction sheet
NC
Common
NO
STEP 1
STEP 7A
Installation
AUT Mode
(Automatic Control)
Caution:
Recommended
Ensure that the
orientation
STEP 6
product is installed on
STEP 7B
PROGRAMMING
a flat rigid surface.
A - Software
AUT Mode
B - Keypad
(Remote Control)
STEP 7C
20
Manual Mode
Door cut-out for
front panel.
STEP 7D
Padlocking Mode
STEP 4
ATyS p 800 to 1000 A
ø 9
ø 15
8.5
33
8.5
15.75
50
STEP 3
Recommanded to use SOCOMEC
Example: Control wiring for a 400VAC application having a 3 phase and neutral supply.
Voltage Sensing Kit
(refer to ATyS p
accessories
for details)
2
ATS Power Supply
Input I
Power supply I - L
Power supply I - N
208-277 VAC ±20%:
50/60 Hz
ATS Voltage Sensing
Input
Source supply I
S I - Phase 1
S I - Phase 2
S I - Phase 3
600 VAC (ph-ph) max
S I - Neutral
332 VAC (ph-n) max
ATS Module
Control Inputs
(Programmable)
ATyS p
ATS CONTROLLER
5
Dual auxiliary supply:
ATS Module
Uc 208-277V~ +/-20% 50/60Hz
Power comsumption: 22VA
Output Contact
(Programmable)
See instruction sheet
Remote interface
RJ45 - to ATyS D20
M
Ok
Ok
138
T
M
ATyS p 1250 A
ATyS p 1600 to 3200 A
16 x 11
ø12.5
T
5
5
800 A
3 P
4 P
3 P
M
255
335
255
25
25
30
30
T
80
80
80
28.5
15.75
45
45
60
90
C
391
391
391
STEP 2
Power Terminal Connections
To be connected using terminal lugs, rigid or flexable busbars.
Minimum cable section Cu (mm
) at Ith
2
(IEC 60947-1)
Recommended cable section Cu (mm
2
) at Ith
Maximum cable section Cu (mm
2
)
Maximum Cu busbar width (mm)
Type of screw
Recommended tightening torque (N.m)
Maximum tightening torque (N.m)
1
LOAD
R1 R2 S1 S2 T1 T2
1
1. Position 0 order
ATyS D20
2. Position 1 order
Remote Control /
6
7
8 9
Display Unit
3. Position 2 order
4. Zero position priority order
312 313 314 315 316 317
63A 64A 24 14 04 13
5. Remote Control Enable (Priority over Auto)
6. Product Available output (Motor)
4 3 2 1
7. Position II aux contact
8. Position I aux contact
9. Position 0 aux contact
10. O/P to ATyS D20 remote unit
11. Programmable Output Contact.
ATyS p 800 to 1600 A
Dimensions
51,5
C
21
ATyS p 2000 to 3200 A
51.5
C
21
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
4 P
3 P
4 P
3 P
4 P
3 P
4 P
3 P
4 P
3 P
335
255
335
347
467
347
467
347
467
347
80
80
80
120
120
120
120
120
120
120
391
391
391
391
391
523
523
523
523
523
FRAME B6
FRAME B7
FRAME B8
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
2x185
-
-
-
-
-
2x50x5
2x60x5
2x60x7
2x100x5
3x100x5
4x100x5
3x100x10
2x300
4x185
4x185
6x185
-
-
63
63
63
100
100
100
M8
M8
M10
M12
M12
M12
8.3
8.3
20
40
40
40
13
13
26
45
45
45
STEP 3
CONTROL / COMMAND Terminals
Ensure that the product is in Manual Mode.
1
12-15. Programmable Inputs 1-4
2
preferred source
alternate source
16-17. Programmable Inputs 5-6
18. Aux. Supply (207/210) to be used
with ATyS optional I/O modules
19. Contact "Start/Stop Genset" : if S1
is not available the NC contact le
contact (71-72) is close
20. Contact "Start/Stop Genset" : if S1
is not available the NO contact le
contact (71-74) is open
21. Option Module Slots 1 to 4
22. Current Transformer incoming cable
connections
By default set to ATS Product
23. Voltage Sensing Inputs
Available - Normally Open
24. Power Supply Inputs
in mm.
4 P
467
120
523
-
-
100
M12
40
45
2

Advertisement

loading

Summary of Contents for socomec ATYS P

  • Page 1 Power supply I - N LOAD • ATyS D20 Interface (remote control / display unit). 208-277 VAC ±20%: 208-277 VAC ±20%: • RJ45 cable for ATyS D20 => ATyS p. 50/60 Hz 50/60 Hz • Voltage sensing kit. • Current transformers. • Plug-in optional modules: RS485 MODBUS...
  • Page 2 Communication between the software and the ATyS p may be done through the Ethernet/Modbus TCP or Modbus RTU modules PROG that are available as an option. The ETHERNET / MODBUS modules are to be installed in one of the slots provided in the ATYS p ATS control unit.