Huawei FusionModule5000 Maintenance Manual page 62

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
2.
3.
If any of the preceding conditions occur, troubleshoot the magnetic lock as follows:
1.
2.
3.
4.
Figure 5-27 Adjusting the gaps between the electromagnets and the magnetic iron plates
Figure 5-28 Flap for adjusting heights of magnetic iron plates
Issue 01 (2016-10-18)
Check whether the magnetic iron plates align with the electromagnets.
Check whether gaps exist between the magnetic iron plates and the electromagnets.
Check the circuit and rectify any circuit fault.
Adjust the magnetic iron plate base and door panels to ensure that the magnetic iron
plates align with the electromagnets. Ensure that the position deviation is no too large.
If gaps exist between the electromagnets and the magnetic iron plates, rectify the fault by
referring to
Figure
5-27.
If the magnetic iron plates are not level with each other, adjust them by using the flap
shown in
Figure
5-28.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
56