Figure 5-14 Removing a skylight magnetic lock
Step 4 Install a new skylight magnetic lock and tighten the two screws.
Step 5 Connect cables to the new skylight magnetic lock to the cables cut off in
end terminals.
Step 6 Close the rotating skylight. Power on and off the skylight for three consecutive times and
check that the skylight can open properly.
----End

5.4.10 Replacing the Water Sensor and Water Detection Cable

The water sensor can be installed in various scenarios. This section describes the general
method for replacing the water sensor.
Prerequisites
Context
Prepare a water sensor or water detection cable of the same model.
A water sensor consists of a water detection cable, water sensor, and conversion cable. The
water detection cable is laid out on the floor, connected to the water sensor placed near the
collector by the conversion cable.
Issue 01 (2016-10-18)
The water sensor needs to be replaced.
A spare water sensor of the same model is available and functional.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 5-15
shows the components.