Item
Double door
magnetic lock
function
2.5 Routine Maintenance for the Fire Extinguishing
System

2.5.1 Routine Maintenance for the Smoke Detector

Table 2-14 Routine maintenance for the smoke detector
Item
Smoke detector
indicator
Issue 01 (2016-10-18)
Maintenance
Method
Interval
Monthly
Check whether
the magnetic
lock attracts
and separates
properly when
being powered
on and off
respectively.
Maintenance
Method
Interval
Quarterly
Observe and
check whether
the indicator on
the smoke
detector is
normal.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Routine Maintenance
Expected
Exception
Result
Handling
The magnetic
If the magnetic
lock attracts
lock fails to
and separates
attract or
properly.
separate
properly,
replace the lock
by referring to
5.4.13
Replacing a
Double-Door
Magnetic
Expected
Exception
Result
Handling
The indicator
If the indicator
blinks once
blinks twice
every 6
every 6 seconds
seconds. (The
or does not
interval varies
blink, the
with sensors.
smoke detector
See the product
is faulty or the
instructions.)
cables are not
properly
connected.
Check the
cables or
replace the
smoke detector.
Lock.