Setting The Field Bus Baud Rate; Setting The Field Bus Protocol - Festo VIFB-02- Series Manual

Valve terminal/valve sensor terminal with field bus connection
Hide thumbs Also See for VIFB-02- Series:
Table of Contents

Advertisement

VIFB1 – 02
DIL switch
1
2
3
4
ON
Fig. 4/19: Setting the field bus baud rate
DIL switch
1
2
3
4
ON
Fig. 4/18: Setting the field bus protocol
> IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 <
9604
4. Installation

Setting the field bus baud rate

PLEASE NOTE
The field bus baud rate should be set on the
valve terminal/valve sensor terminal so that
it agrees with the setting on the field bus
module (master) of the control system.
Klöckner-Moeller systems:
Please note that with Klöckner-Moeller cont-
rol systems only the field bus baud rate
187.5 kBaud is permitted.
Field bus baud rate [kBaud]
31.25
62.5
1
1
2
2

Setting the field bus protocol

The setting depends on the control system used.
Festo
3
4
ON
187.5
1
2
Control system
Klöckner-Moeller
Klöckner-Moeller
Klöckner-Moeller
3
4
ON
375
1
2
Siemens
3
4
ON
4-27