1. Installation

1.3.2 Field bus baud rate and field bus length

Baud rate
Field bus length
(in kBaud)
maximum
125
500 m
250
250 m
500
100 m
1000
20 m
Fig. 1/12: Max. field bus and branch line lengths depending on the baud rate
Festo P.BE-CP-CO2-EN en 0107NH
The maximum permitted field bus length depends on the
baud rate used. Fig. 1/12 shows the guideline values. De-
tailed information can be found in the manuals for your con-
trol system or bus interface.
The maximum permitted length of the branch line depends on
the total length of the branch lines and the baud rate.
Please note
S Refer to the manuals for your control system or bus in-
terface for information on the T-adapter and the maxi-
mum branch line length which is permitted for your con-
troller.
S When ascertaining the maximum permitted length of the
field bus cable, take into account also the sum of the
branch line lengths.
Branch line length
maximum
20 m
10 m
5 m
1 m
Information on setting the baud rate can be found in chapter
1.2.2.
Total length of the
branch lines
maximum
100 m
50 m
25 m
5 m
1-17