SmartPLC SafeLine AC4S with fieldbus interfaces
Parameter data
Parameter
Data type
IN_Channel_A
INT
IN_Channel_B
INT
EnableIN_Test
BOOL
DisableLogging
BOOL
EnableStartupTest
BOOL
SynchTime
WORD
StabilisingTime
WORD
* ...
Default value
>
Process data
Parameter
Data type
S_IN_dep_filter_testreq
SAFEBOOL Safe process signal
>
Description
Local input to which sensor
channel A is connected.
Local input to which sensor
channel B is connected.
Evaluation of a test signal which
was created by a local output
Transmission of the event
messages to OSC of the device
Control execution of the start-up
test
Synchronisation time
Max. bounce time
Description
Possible values
1
Local input IN1
...
...
8
local input IN8
1
Local input IN1
...
...
8
local input IN8
FALSE
Test signal is ignored *
TRUE
Test signal is evaluated
FALSE
Following states of the state diagram
are transmitted to the OSC: *
S_ON
S_OFF
S_Test
S_Error
S_Init (HW-Error)
TRUE
Following states of the state diagram
are transmitted to the OSC:
S_Test
S_Error
S_Init (HW-Error)
FALSE
No start-up test *
TRUE
Start-up test is executed; slave waiting
for start-up sequence OFF  ON
0
Infinite
250
250 milliseconds
...
...
500
500 milliseconds *
...
...
60000
60000 milliseconds
250
250 milliseconds *
...
...
10000
10000 milliseconds
Possible values
FALSE
SAFE OFF
TRUE
Safe ON
43048
43129
253