IFM Electronic AC402S Programming Manual page 144

Smartplc safeline ac4s with fieldbus interfaces
Table of Contents

Advertisement

SmartPLC SafeLine AC4S with fieldbus interfaces
>
Output parameters
Parameter
Data type
abList_SA_Slave
ARRAY[0..31]
OF BYTE
abList_B_Slave
ARRAY[0..31]
OF BYTE
xReady
BOOL
xBusy
BOOL
xError
BOOL
wDiagnostic
WORD
Diagnostic codes:
0x0000
No specific error is set
0x0F01
Unknown error
0x0F02
Unknown/invalid target
0x0F03
Unknown command ID
0x0F04
Invalid parameters
0x0F05
Timeout during processing
144
Description
List of output parameters of S/A
slaves in the selected AS-i master.
Each byte contains the output
parameters of an AS-i slave.
– byte 0 (LSB) = res.
– byte 1 = slave with address 1(A) ...
– byte 31 = slave with address 31(A)
List of output parameters of B slaves
in the selected AS-i master. Each byte
contains the output parameters of an
AS-i slave.
– byte 0 (LSB) = res.
– byte 1 = slave with address 1B
...
– byte 31 = slave with address 31B
Signal indicates whether the execution
of the FB is completed.
Signal indicates whether the FB is
being executed.
Signal indicates whether errors
occurred while the FB was executed.
Diagnostic information
Possible values
Per byte:
Bits 0...3:
P0-P3
Per byte:
Bits 0...3:
P0-P3
FALSE
FB is inactive or being
executed.
TRUE
FB execution is completed.
FALSE
FB is deactivated or FB
execution is completed.
TRUE
FB execution has started but is
not yet completed.
FALSE
FB is disabled or is being
executed or FB was executed
without error.
TRUE
An error occurred while the FB
was executed.
→ List below (Diagnostic codes)
42533

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac422sAc412sAc432s

Table of Contents