Output parameters
Parameter
Data type
xActive
BOOL
wCycleCount
WORD
xError
BOOL
wDiagnostic
WORD
Diagnostic codes:
0x0000
No specific error is set
0xnF01
Unknown error
0xnF02
Unknown/invalid target
0xnF03
Unknown command ID
0xnF04
Unknown parameters
0xnF05
Timeout during processing
Legend:
1
Get_ASi_Data executes the FB ACnnnn_SysCmd sequentially with different command IDs in order to determine the individual
elements of the complex variable. In the returned error code, the nibble n indicates the command request where the error
occurred. n can have the following values:
1 = error with "Get LAS, LDA, LPF, LCE"
2 = error with "Get LPS"
3 = error with "Get CDI"
4 = error with "Get PCD"
5 = error with "Get Input Parameter"
6 = error with "Get Output Parameter"
7 = error with "Get LCEMS, LCEAS, LDAE"
162
Description
Signal confirms the FB execution
Counter for FB cycles that were fully
run through
Signal indicates whether errors
occurred while the FB was executed.
Diagnostic information
1
1
1
1
1
Possible values
FALSE
Function block is inactive
TRUE
FB is active (=is executed)
Number in hexadecimal representation
FALSE
FB is disabled or is being
executed or FB was executed
without error.
TRUE
An error occurred while the FB
was executed.
→ List below (Diagnostic codes)
42609